Permit Number: T22CM07266
Parcel: 136260900

Address:
3120 S BECK DR

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM07266
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2022 RPARSON1 OIP REVIEW Completed
09/29/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM07266

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
Denied
Main breaker replacement may not negatively affect the equipment integrity or listing, NEC 110.3. Provide an electrical load calculation if reducing the main breaker rating.


PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
09/29/2022 VVERA1 OUT TO CUSTOMER Completed