Permit Number: T22CM07206
Parcel: 13416205D

Address:
7149 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM07206
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2022 SHASEMA1 ENGINEERING REVIEW Passed
09/26/2022 JPEELDA1 FIRE REVIEW Approved
10/05/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/05/2022 ROBERT SHERRY WATER REVIEW Completed
10/05/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Faucets serving lavatories in all buildings other than R3 occupancies, individual units in R2 occupancies, or International Residential Code structures shall be automatic faucets dispensing a maximum of 0.25 gallons per cycle. The cycle time shall not be less than ten-seconds for accessibility. Reference: Section 419.6, IPC 2018 as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Provide tempered water for the lavatory using an approved device conforming to ASSE 1070. Reference: Sections 419.5 and 607.1.2, IPC 2018.
3. The specified water heater is not tankless, It stores four gallons of hot water. Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503.1, 504, 606.1, and 607.3, IPC 2018.
10/06/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/14/2022 WILDAN BUILDING-COMMERCIAL REVIEW Completed
10/17/2022 STEVE SHIELDS ZONING REVIEW Approved
10/17/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed