Permit Number: T22CM07136
Parcel: 117131560

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM07136
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2022 VFLORES1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change Please contact Pima County Addressing to request an address Phone #:520-724-9512 Email: addressing@pima.gov
09/19/2022 SHASEMA1 ENGINEERING REVIEW Passed
09/22/2022 PSHELTO1 FIRE REVIEW Approved
10/04/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/04/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/04/2022 ROBERT SHERRY WATER REVIEW Completed
10/05/2022 PAUL CAMARENA ZONING REVIEW Approved
10/05/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
10/05/2022 PCAMARE1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/18/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM07136

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Denied
Sheet C1 Show path of travel to accessible parking and the public way
Sheet A1 Show ADAAG restrooms per IBC P(table 2902.1
Sheet A1 Provide Expanded Restroom details. Provide Accessible Signage for restrooms.
Sheet A1 Field verify existing door hardware for ADAAG compliance.
Sheet A1 Provide details for Hand sink showing ADAAG compliance.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov