Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T22CM07090
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/16/2022 | SHASEMA1 | ENGINEERING | REVIEW | Passed | |
| 09/20/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T22CM07090 624 N Loquat Ave - R-1 Enclose Carport to Bedroom & add Carport (1st Review) TRANSMITTAL: September 20, 2022 This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10. COMMENT: Resubmit revised drawings and a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf. Once the required plot plan is provided additional comments maybe forth coming. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
| 09/29/2022 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T22CM07090 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. Place the code reference on the plans. Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits SITE PLAN: Provide a site plan showing all buildings, R106.1.1. Show the location of utility lines to the building. FLOOR PLAN: Provide a floor plan showing each proposed room with labeled function and dimensions. Show door locations and window sizes with type identified as XO or SH. Include the identification of adjacent rooms with door or window opening into the proposed space. SECTIONS - DETAILS: Show a complete cross-section detail of the new exterior wall, R106.1.1. Show the minimum 12” x 12” continuous #4 rebar reinforced footing, R403.1. Show exterior wood siding, sheathing and wall framing anchored with ½” x 10” bolts and with pressure treated sill. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground, R317.1 item 5. The framed wall may require a stem for achieving the 6” clearance between framing and ground (R317.1 item 5) or the floor level could be raised a minimum of 6” above grade. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF. MECHANICAL PLANS: Provide equipment details showing code compliant components, locations and sizes. ELECTRICAL PLANS: Provide proposed wiring details showing code compliant device locations and circuit sizes. Show circuit number and size with receptacles at all walls (within 6’ of any wall location) and lighting control at each doorway both interior and exterior. Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors requires combination type arc-fault circuit interrupters, E3902.16. INTERNATIONAL ENERGY CONSERVATION CODE: Provide insulation details minimum (R-13 walls and R-30 small additions or otherwise R-38 ceiling) showing code compliant placement of materials and ratings, N1101. Windows require a solar heat gain of 0.25 or better. If you have any questions, please contact: Ken Van Karsen (520) 837-4912 City of Tucson Residential Plan Review |
| 10/04/2022 | JCARLTO1 | NPPO | REVIEW | Passed |