Permit Number: T22CM07088
Parcel: 12912177A

Address:
1102 E 30TH ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM07088
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review


PROJECT:
T22CM07088
1102 E 30th St - R-2
Detached shade structure (1st Review)

TRANSMITTAL: September 16, 2022
Provided a detail comment response letter with your submittal that clearly shows how you have addressed all comments with your next submittal.

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10.

Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A.

1. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). Perimeter Yard setbacks for a structure such as the one proposed are measured from the post supporting the roof. As setback dimensions were not provided Zoning can not provide comment on the proposed setbacks. within a perimeter yard and is detached from a principal structure shall comply with the perimeter yard width standards of the principal structure, except that the accessory structure may be built to a parcel line with the consent of the adjoining or, when separated by an alley, adjacent property owner(s). To secure this neighbor setback waiver the following statement must be provided on the plot plan and be signed and dated by the adjacent property owner(s):
My Name is____________________ and I am the owner of the property located at_______________________. I have reviewed the site plan and I have no objection to structure being located or constructed________ feet from the property line as depicted on the site plan.

Signature: _____________________________

Date: _________________________________
2. Based on aerial photos there is a detached structure located west of the existing house that is not shown on this Zoning was not able to find an approved compliance review or permit for this structure. If this structure is less than 200 sq. ft. a building permit is not required but a Zoning compliance review is. Show this structure on the plot plan along with perimeter yard setback dimensions.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
09/16/2022 SHASEMA1 ENGINEERING REVIEW Passed
09/30/2022 JCARLTO1 NPPO REVIEW Approved
10/05/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T22CM07088
PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.
GENERAL REQUIREMENTS:
The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.
SITE PLAN:
1. Show the location of utility lines on the property, R106.1.1. Identify the utility lines requiring upgrade or replacement (i.e., Overhead Electrical Line).
FOUNDATION PLAN:
1. Dimension the footing length, width, and depth into undisturbed soil for each footing type and condition, R403.1. Show the minimum 12” reinforced footing depth below the undisturbed ground surface R403.1. Show #4 rebar reinforcement with 3” clearance from earth, R403.1.3.5.3.

SECTIONS - DETAILS:
1. The roof structure may not extend to a point closer than 3 feet from the neighboring property line without fire rated protection for fire spread. Provide compliance with R302.1 (City of Tucson Amended) by removing the porch roof within 3 feet to the (east) property line or provide a complete wall barrier with not less than one-hour fire-resistive construction in compliance with IBC Table 721.1(2).
Please contact the plans reviewer if you have any questions:
Ken Van Karsen
520 837-4912
City of Tucson Residential Plan Review