Permit Number: T22CM07077
Parcel: 137115630

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM07077
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review


PROJECT:
T22CM07077
1454 W Breakwell St - R-3 RCP
Enclose Porch (1st Review)

TRANSMITTAL: September 16, 2022
Provided a detail comment response letter with your submittal that clearly shows how you have addressed all comments with your next submittal.

This site is located in the R-3 zone (UDC 4.7.12). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6.

1. The side perimeter yard setbacks listed and shown on the plan are not correct. This subdivision was developed as a Residential Cluster Project (RCP) and the interior perimeter yard setbacks are 3’-0”.

2. Based on aerial photos there is some type of accessory structure that shows up sometime after 2020. Zoning was not able to find an approved compliance review or permit for this structure. If this structure is less than 200 sq. ft. a building permit is not required but a Zoning compliance review is. Show this structure on the plot plan along with perimeter yard setback dimensions. If either setback is less than the allowed 3’-0” list above a neighbor’s setback waiver is required. To secure this neighbor setback waiver the following statement must be provided on the plot plan and be signed and dated by the adjacent property owner(s):
My Name is____________________ and I am the owner of the property located at_______________________. I have reviewed the site plan and I have no objection to structure being located or constructed________ feet from the property line as depicted on the site plan.

Signature: _____________________________

Date: _________________________________


If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
09/16/2022 SHASEMA1 ENGINEERING REVIEW Passed
09/30/2022 JCARLTO1 NPPO REVIEW Approved
10/04/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Show the functional name of each proposed room and each adjacent room, R106.1.1. Existing bedrooms with removed windows must show code compliance for egress, R310.