Permit Number: T22CM07052
Parcel: 13317064B

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM07052
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2022 SHASEMA1 ENGINEERING REVIEW Passed
09/20/2022 JVINCEN1 FIRE REVIEW Approved
09/22/2022 WBERGER1 ZONING REVIEW Approved
09/22/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/27/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM07052

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
NOTE: Every effort has been made to identify the code violations. Any oversight by the review team shall not be considered an authority to violate, set aside, cancel or alter applicable codes or ordinances. The plan review and permit issuance shall not be considered a warranty or guarantee. The Structural Engineer is responsible for following ALL applicable Federal, State and local Municipal Codes and Ordinances.


BUILDING REVIEW COMMENTS:
Denied
1. Sheet G2.0: The occupant load is calculated incorrectly. Occupant load calculations are based on a space by space calculation in accordance with Section 1004.3. They large waiting room has not been included in the calculations.
Provide an updated occupant load calculation in accordance with Section 1004.3 and Table 1004.5.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
First Plumbing Review:
1). Address Building plan review occupant load related comment before a complete plumbing review can be done. -IPC 403.1
2). Show existing required high/low drinking fountain in this suite or the travel idstance if located in a common area elsewhere. -IPC 403.1, 403.5


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
10/13/2022 ROBERT SHERRY WATER REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
10/13/2022 NGARCIA3 OUT TO CUSTOMER Completed