Permit Number: T22CM07047
Parcel: 13316024L

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM07047
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2022 SSHIELD1 ENGINEERING REVIEW Passed
09/22/2022 STEVE SHIELDS ZONING REVIEW Approved
09/22/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/27/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM07047

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Refer to Mechanical Drawing M2, Detail 102 shows Ceiling Mounted Exhaust Fans. The Detail shows, it is hung from the bottom chord of the steel joists. The loading on the joists is off panel point. Verify if any reinforcing is required to the existing steel joists.
Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.


BUILDING REVIEW COMMENTS:
Denied
1. The occupant load is calculated incorrectly. Occupant load calculations are based on a space by space calculation in accordance with Section 1004.3. They gym has not been included in the calculations. Provide an updated occupant load calculation in accordance with Section 1004.3 and Table 1004.5.
2. Sheet G2: Provide clarification on the exit discharge portion of the egress path. It appears that central portion of the building is open to the air and not within the structure of the building. If this is true no further comment is to be made however, if it not true comply with the applicable requirements of Section 1028.
3. Sheet G2: Provide the travel distance to the existing restrooms.
4. Sheet G2: Provide clarification on adjacent tenants to ensure proper separation.
5. Cover page: Provide the required plumbing fixture calculations.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
First Plumbing Review:
1). Need to address Building review comments 1,3,5 that refer to occupancy load, travel distance to existing restrooms & drinking fountain & plumbing fixture calcs. before a complete plumbing review can be done -IPC 403.1, 403.5
2). Enlarge water plan on page P2 missing water to toilet. -IPC 604.5


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
10/04/2022 JPEELDA1 FIRE REVIEW Approved
10/12/2022 ROBERT SHERRY WATER REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
10/13/2022 VVERA1 OUT TO CUSTOMER Completed