Permit Number: T22CM07027
Parcel: 10321025E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM07027
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2022 SHASEMA1 ENGINEERING REVIEW Passed
09/20/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM07027

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

BUILDING REVIEW COMMENTS:
Denied
NOT A VALID CONSTRUCTION TYPE
PROVIDE THE AREA OF THE TENANT SPACE
PROVIDE DESCRIPTION OF THIS FEATURE
PROVIDE INSTALLATION DETAILS FOR ACOUSTIC ROOF TILE

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
09/21/2022 PSHELTO1 FIRE REVIEW Approved
09/23/2022 STEVE SHIELDS ZONING REVIEW Approved
09/23/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/03/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/03/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/03/2022 ROBERT SHERRY WATER REVIEW Completed
10/05/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved