Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM07015
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/19/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The site plan shows five buildings; will all of the buildings be connected to the public sewer? 2. An approved 2-way cleanout fitting is allowed to be used at the junction of a building drain and a building sewer; otherwise, cleanouts shall open to allow cleaning in the direction of flow. Reference: Section 708.1.8, IPC 2018. 3. Provide the rim elevation of the next upstream sanitary manhole, 8142-14, and the first-floor elevation for each building that will be connected to the public sewer. Determine the need for backwater valves per Section 714.1, IPC 2018, as amended by the City of Tucson. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/19/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |