Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM07010
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/14/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM07010 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied Please make corrections and resubmit. Resubmittal shall include a response letter. All code references are to the IRC edition as adopted by Tucson, AR & City of Tucson Amendments to the 2018 IRC unless otherwise noted. Recommend clouding changes to speed up the rereview. 1. Comment #1-“Roof framing has changed to trusses”. a. Therefore, provide documentation and details of the Wood Trusses, required to be designed, engineered & manufactured as per shop drawings prepared by truss manufacturer & stamped by a Design Professional as per IRC R802.10 with supporting calculations. b. Provide documentation and details of the required Truss Design Drawings. Truss design drawings, prepared in conformance to Section R802.10.1, shall be provided to the building official and approved prior to installation. Truss design drawings shall be provided with the shipment of trusses delivered to the job site. Truss design drawings shall include, at a minimum, the following information as per IRC-R802.10.1: 1) Slope or depth, span and spacing. 2) Location of all joints. 3) Required bearing widths. 4) Design loads as applicable. c. Provide documentation and details of the required Design of the Wood trusses. Wood trusses shall be designed in accordance with accepted engineering practice. The design and manufacture of metal-plateconnected wood trusses shall comply with ANSI/TPI 1. The truss design drawings shall be prepared by a registered professional where required by the statutes of the jurisdiction in which the project is to be constructed in accordance with Section R106.1 as per IRC-R802.10.2. d. Provide documentation and details of the required Bracing Trusses shall be braced to prevent rotation and provide lateral stability in accordance with the requirements specified in the construction documents for the building and on the individual truss design drawings. In the absence of specific bracing requirements, trusses shall be braced in accordance with accepted industry practice such as the SBCA Building Component Safety Information (BCSI) Guide to Good Practice for Handling, Installing & Bracing of Metal Plate Connected Wood Trusses as per IRC- R802.10.3. 3. Required Inspections to be provided as per AHJ & associated 3rd Party Inspection Agency. BUILDING REVIEW COMMENTS: Denied NPR T22CMO7010 (BLDG) KSW 4th ST, TUC AZ 10-13-22 (1 Hr.) Please make corrections and resubmit. Resubmittal shall include a response letter. All code references are to the IRC edition as adopted by Tucson, AR & City of Tucson Amendments to the 2018 IRC unless otherwise noted. Recommend clouding changes to speed up the rereview. 1. Comment #1-“Roof framing has changed to trusses”. a. Therefore, provide documentation and details of the Wood Trusses, required to be designed, engineered & manufactured as per shop drawings prepared by truss manufacturer & stamped by a Design Professional as per IRC R802.10 with supporting calculations. b. Provide documentation and details of the required Truss Design Drawings. Truss design drawings, prepared in conformance to Section R802.10.1, shall be provided to the building official and approved prior to installation. Truss design drawings shall be provided with the shipment of trusses delivered to the job site. Truss design drawings shall include, at a minimum, the following information as per IRC-R802.10.1: 1) Slope or depth, span and spacing. 2) Location of all joints. 3) Required bearing widths. 4) Design loads as applicable. c. Provide documentation and details of the required Design of the Wood trusses. Wood trusses shall be designed in accordance with accepted engineering practice. The design and manufacture of metal-plate connected wood trusses shall comply with ANSI/TPI 1. The truss design drawings shall be prepared by a registered professional where required by the statutes of the jurisdiction in which the project is to be constructed in accordance with Section R106.1 as per IRC-R802.10.2. d. Provide documentation and details of the required Bracing. Trusses shall be braced to prevent rotation and provide lateral stability in accordance with the requirements specified in the construction documents for the building and on the individual truss design drawings. In the absence of specific bracing requirements, trusses shall be braced in accordance with accepted industry practice such as the SBCA Building Component Safety Information (BCSI) Guide to Good Practice for Handling, Installing & Bracing of Metal Plate Connected Wood Trusses as per IRC- R802.10.3. 2. Emergency Escape and Rescue Openings in bedroom documentation. Approved 3. Provide documentation & details of Smoke Alarms. Although E2.0 shows combo “SDCM” alarm inside the bedroom, it does not show “outside sleeping area” as per IRC-R314.3. Provide additional interconnected SD alarm outside bedroom. a. Location-Smoke alarms shall be installed in the following locations: In each sleeping room. Outside each separate sleeping area in the immediate vicinity of the bedrooms as per IRC-R314.3. b. Interconnection-Where more than one smoke alarm is required to be installed within an individual dwelling unit in accordance with Section R314.3, the alarm devices shall be interconnected in such a manner that the actuation of one alarm will activate all of the alarms in the individual dwelling unit. Physical interconnection of smoke alarms shall not be required where listed wireless alarms are installed and all alarms sound upon activation of one alarm as per IRC-R314.4. d. Listings-Smoke alarms shall be listed in accordance with UL 217. Combination smoke and carbon monoxide alarms shall be listed in accordance with UL 217 and UL 2034 as per IRC-R314.1.1. 4. Provide documentation & details of CO Alarms. Addressed in #3 Comments. 5. Verify Drainage. Approved upon final inspection. 6. Roof Framing Plan information-See Comment #1. 7. See Comment #2. 8. See Comment #3. 9. See Comment #4. 10. See Comment #5. 11. A Vapor barrier is required by code. Provide a 6-mil polyethylene or approved vapor retarder with joints lapped not less than 6 inches shall be placed between the concrete floor slab and the base course or the prepared subgrade where a base course does not exist as per IRC-R506.2.3. 12. Required Inspections to be provided as per AHJ & associated 3rd Party Inspection Agency. MECHANICAL REVIEW COMMENTS: Approved ELECTRICAL REVIEW COMMENTS Denied 5. Provide documentation & details of Smoke Alarms. Although E2.0 shows combo “SDCM” alarm inside the bedroom, it does not show “outside sleeping area” as per IRC-R314.3. Provide additional interconnected SD alarm outside bedroom. a. Location-Smoke alarms shall be installed in the following locations: In each sleeping room. Outside each separate sleeping area in the immediate vicinity of the bedrooms as per IRC-R314.3. b. Interconnection-Where more than one smoke alarm is required to be installed within an individual dwelling unit in accordance with Section R314.3, the alarm devices shall be interconnected in such a manner that the actuation of one alarm will activate all of the alarms in the individual dwelling unit. Physical interconnection of smoke alarms shall not be required where listed wireless alarms are installed and all alarms sound upon activation of one alarm as per IRC-R314.4. d. Listings-Smoke alarms shall be listed in accordance with UL 217. Combination smoke and carbon monoxide alarms shall be listed in accordance with UL 217 and UL 2034 as per IRC-R314.1.1. 6. Provide documentation & details of CO Alarms. Addressed in #3 Comments. 9. Required rough and final electrical Inspections to be provided as per AHJ & associated 3rd Party Inspection Agencies. 10. Required Inspections to be provided as per AHJ & associated 3rd Party Inspection Agency. PLUMBING REVIEW COMMENTS: Approved If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
| 10/20/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved |