Permit Review Detail
Review Status: Active
Review Details: 3RD PARTY REVIEW - COMMERCIAL TI
Permit Number - T22CM07008
Review Name: 3RD PARTY REVIEW - COMMERCIAL TI
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/13/2022 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | RECEIVED | |
| 09/13/2022 | ANY | 3RD PARTY REVIEW-COMMERCIAL | AT 3RD PARTY OFFICE | Active | |
| 09/19/2022 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/19/2022 | WBERGER1 | ZONING | REVIEW | Approved | |
| 10/04/2022 | JPEELDA1 | FIRE | REVIEW | Reqs Change | The building or structures constructed shall be within 400' of a fire hydrant and or additional hydrants shall be installed or fire sprinklers throughout the complete building. Hydrants in place exceed 400'. Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 Fire Plans Examiner Tucson Fire Department |
| 10/04/2022 | LEVANS2 | ENGINEERING | REVIEW | Reqs Change | Include a site plan that shows stormwater drainage flow lines for existing buildings and pavement as well as the proposed stormwater drainage for the expansion. Lianne Evans lianne.evans@tucsonaz.gov |
| 10/11/2022 | ROBERT SHERRY | WATER | REVIEW | Completed |