Permit Number: T22CM06974
Parcel: 134234150

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM06974
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2022 SHASEMA1 ENGINEERING REVIEW Passed
09/16/2022 WBERGER1 ZONING REVIEW Approved
09/16/2022 PSHELTO1 FIRE REVIEW Approved
09/16/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/22/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM06974

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Denied

Sheet G1 Show location of water cooler on floor plan.
Sheet A2 Provide splay wire maximum 8' from wall.
Sheet A4 Provide details of existing restrooms showing ADA Compliance, since it serves the TI.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
10/03/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/03/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/03/2022 ROBERT SHERRY WATER REVIEW Completed
10/04/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 Provide a floor receptacle(s) in the conference room and all wall areas was as required per NEC art 210.71.

2 New Exit fixtures shall be connected to the area unswitched lighting circuit. NEC art 700.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.