Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM06971
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/10/2022 | WBERGER1 | ZONING | REVIEW | Approved | |
| 10/17/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 10/17/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The manufacturer's literature still requires a running water connection for the appliance. Provide the full installation instructions. [Initial comment: Provide information to show that the installation of the chocolate fountain complies with the manufacturer's listing requirements (e.g. a water connection is required). Reference: Section 303.2, IPC 2018.] 2. Comment not addressed. [Initial comment: Verify that the chocolate fountain does not utilize domestic water as a single-pass coolant. Reference: Section 930, IMC 2018, as amended by the City of Tucson.] |