Permit Number: T22CM06969
Parcel: 10603167D

Address:
351 W PRINCE RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM06969
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2022 SHASEMA1 ENGINEERING REVIEW Passed
09/22/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM06969

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Appproved


BUILDING REVIEW COMMENTS:
Denied
1. The occupant load is not calculated properly. The space contains a large conference that needs to be included in the occupant load calculation. Based on occupant load calculations additional exit may be required. Provide a corrected occupant load calculation and update all applicable requirements.
2. Provide information on the adjacent tenants to ensure proper separation.


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Denied
1. Provide the location of egress illumination in accordance with Section 1008


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
09/22/2022 SAMUEL ROGERS ZONING REVIEW Approved
09/22/2022 SROGERS2 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/27/2022 JVINCEN1 FIRE REVIEW Approved
10/11/2022 ROBERT SHERRY WATER REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
10/11/2022 VVERA1 OUT TO CUSTOMER Completed