Permit Number: T22CM06958
Parcel: 11012089C

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM06958
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2022 JVINCEN1 FIRE REVIEW Approved
09/21/2022 SSHIELD1 ENGINEERING REVIEW Passed
09/21/2022 STEVE SHIELDS ZONING REVIEW Approved
09/22/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM06958

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Denied

SPECIFY 2018 INTERNATIONAL BUILDING CODE
PROVIDE OCCUPANCYCLASSIFICATION FOR RAMADA IBC 302.1
PER IBC TBL 2308.7.2(2) THE MAX. SPAN OF 2X8 D.F.#2 RAFTERS @ 24" O.C. IS 14-10.
PROVIDE REFERENCE TO THE I.B.C FOR WOOD FRAMING
PROVIDE REFERENCE TO IBC CHAPTER 19 FOR CONCRETE


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
09/22/2022 VVERA1 OUT TO CUSTOMER Completed