Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM06930
Parcel: 136350880

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM06930
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2022 NMARTEL1 ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review


PROJECT:
T22CM06930
8437 E Rolling Ridge st - R-1
Home Theather & Garage Addition (1st Review)


TRANSMITTAL: September 16, 2022
COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A. As height dimensions from design grade were not provided, 6” has been added to the heights provided on the elevations to determine perimeter yard setbacks.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A).
1. Based on a wall height of 12’-2” the required perimeter yard setback from the proposed garage to the east property line is 8’-2”, proposed setback is 1’-7”

A Design Development Option (DDO) must be submitted and approved to reduce the required setback,
DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov.

The following comments need to be addressed:
2. The plot plan shall be drawn at an engineering scale, i.e. 1” = 10’, 1” = 20’ etc.

3. Provide a dimension from the centerline of Rolling Ridge St to the face of curb and from the face of curb to the north property line.

4. As the proposed ‘HOME THEATER” qualifies as a bedroom, see UDC Article 11.4.3 definition of Bedroom, provide a full floor plan of the existing SFR so that vehicle parking space requirements can be verified, see UDC Article 4.9.7.B.7.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
09/12/2022 SHASEMA1 ENGINEERING REVIEW Passed
09/26/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM06930


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
Please make corrections and resubmit. Resubmittal shall include a response letter. All code references are to the IRC edition as adopted by Tucson, AR & City of Tucson Amendments to the 2018 IRC unless otherwise noted. Recommend clouding changes to speed up the rereview.
1. Revise drawings with exterior footings at least 12 inches below undisturbed ground surface as per 2018 IRC Section R403.1.4.
2. Revise drawings with anchor bolts at maximum of 6 feet on center and no fewer than two bolts per plate section for wood sole plates and sill plateson concrete floor slab, concrete, and masonry foundation/walls (other than braced wall sections) as per 2018 IRC Section R403.1.6.
3. Revise plans with roof framing details to include framing members, lumber type, grade, size, span, dimensions, spacing, anchoring and attachment information as per 2018 IRC Section R802.3-802.5.
4. Uplift resistance to minimize microburst effects shall be determined by either method 1 or 2 below as per 2018 IRC Amend Section R802.11.1 Uplift resistance:
1) Design-based wind uplift criteria.
Wind uplift requirements shall be determined by using the design wind value of 115 mph within Table R802.11 for the continuous load path transmitting the uplift forces from the rafter or truss ties to the foundation.
2) Prescriptive-based wind uplift criteria.
(Please note that the requirements of this Section are in addition to those required for the structural connection of wood members).
2.1 Conventionally-framed wood or cold-formed steel structures.
All bearing wall vertical connections shall be clipped with either approved structural sheathing or approved clips to provide a continuous load path from the joist or truss through the ledger or top plate to the bottom wall plate. Where clips are used, they shall be minimum Simpson H2.5 (A34 at ledger), or equivalent load capacity, of configuration to match connection and spaced at intervals not to exceed 24". At openings, lower cripple studs do not require clipping but king/trimmer studs require double clips at bottom and upper cripples require both full clipping to header as well as header to king stud. All platform framing requires either strapping listed for the purpose or continuous sheathing over rim joist from stud to stud vertically at each floor level. All non-bearing exterior walls shall be clipped as above except that the spacing may be extended not to exceed every other stud.
2.2. Masonry or concrete structures.
If lateral design requires larger anchors or more conservative spacing, these may be used in lieu of those called out in this Section.
2.2.1. Roof bearing on wall top plate.
Top plates shall be secured to masonry or concrete walls with minimum 0.5" embedded anchor boltsspaced at intervals not to exceed 48". Each joist or truss shall be clipped to plate at bearing with minimum Simpson H2.5 or equivalent loadcapacity and of configuration to match connection. Gable end joists or trusses shall also be clipped at intervals not to exceed 48".
2.2.2. Roof bearing on wall ledger.
Joists or trusses bearing on a wall ledger shall be secured to masonry or concrete walls with minimum Simpson PAI23 purlin anchors or equal with equivalent load capacity listed for the application and embedded into wall per listing at intervals not to exceed 48”. Nonbearing roof diaphragm edges shall have the outermost joist or truss likewise anchored to the wall through blocking.
5. Provide documentation and details of the required Minimum Depth for Exterior footings shall be placed not less than 12 inches below the undisturbed ground surface. Where applicable, the depth of footings shall also conform to IRC-Section R403.1.4.1.
6. Provide documentation and details of the Concrete, Materials for Concrete, and Forms. Materials used in concrete, the concrete itself and forms shall conform to requirements of this section or ACI 318 as per IRC-R404.1.3.3 Concrete, Materials for Concrete, and Forms.
7. Provide documentation and details of the Steel Reinforcement.
Steel reinforcement shall comply with the requirements of ASTM A615, A706, or A996. ASTM A996 bars produced from rail steel shall be Type R. In buildings assigned to Seismic Design Category A, B or C, the minimum yield strength of reinforcing steel shall be 40,000 psi (Grade 40) (276 MPa). In buildings assigned to Seismic Design Category D0, D1 or D2, reinforcing steel shall comply with the requirements of ASTM A706 for low-alloy steel with a minimum yield strength of 60,000 psi (Grade 60) (414 MPa) as per IRC-R404.1.3.3.7.1.
8. Revise drawings with anchor bolts at maximum of 6 feet on center and no fewer than two bolts per plate section for wood sole plates and sill plateson concrete floor slab, concrete, and masonry foundation/walls (other than braced wall sections) as per 2018 IRC Section R403.1.6.
9. Provide documentation and details of the footings & foundation plan for the addition as per IRC-R106.
10. Provide documentation and details of the required wall bracing details and method, including but not limited to the garage as per IRC-R602.10.
a. Show braced wall lines for Family Rm. & Garage addition as per IRC-R602.10.1.
b. Show braced wall panels for Family Rm. & Garage addition as per IRC-R602.10.2.
c. Show required length (minimum) of bracing for Family Rm. & Garage addition as per IRC-R602.10.3 & R602.10.5.
d. Show construction methods for braced wall panels for Family Rm. & Garage addition as per IRC-R602.10.4.
e. Show simplified wall bracing as per IRC-R602.12.
11. Provide documentation and details of the required FASTENING SCHEDULE as per TABLE R602.3(1).
12. Provide documentation and details of the required flashings shall be installed in a manner that prevents moisture from entering the wall and roof through joints in copings, through moisture permeable materials and at intersections with parapet walls and other penetrations through the roof plane as per R903.2.
13. Provide documentation and details of the required Roof decks shall be covered with approved roof coverings secured to the building or structure in accordance with the provisions of this chapter. Roof assemblies shall be designed and installed in accordance with this code and the approved manufacturer's instructions such that the roof assembly shall serve to protect the building or structure as per R903.1.
14. Provide documentation and details of the required Geotechnical Evaluation. In lieu of a complete geotechnical evaluation the load-bearing values in Table R401.4.1 shall be assumed. A complete geotechnical evaluation is required for presumptive load-bearing values greater than 1500 pounds per square foot as per R401.4.1.
15. Provide documentation and details of the required structural beams & headers throughout plan as per R106.1.
16. Provide documentation and details of the non-engineered site-built roofs, and show rafter size, grade, and spacing and wall ties.
17. Provide documentation and details of the continuous load path from the roof to foundation. Specify the type and spacing of all anchors, straps, connectors and clips as per IRC-R301.
18. Provide documentation and details of the required Roof tie-downs as per IRC-R804.3.8.
19. Provide required inspections as per City of Tucson Development Services Department.


BUILDING REVIEW COMMENTS:
Denied
Please make corrections and resubmit. Resubmittal shall include a response letter. All code references are to the IRC edition as adopted by Tucson, AR & City of Tucson Amendments to the 2018 IRC unless otherwise noted. Recommend clouding changes to speed up the rereview.
1. Sheet A-0 Site Plan-Revise site plan drawing with locations, sizes, and meters of building utility lines for gas, water, electric and sewer or septic lines from property line to building as per City of Tucson Amendments to the 2018 IRC-Section R106.1.1.
2. Provide documentation and details of the Exterior walls with a fire separation distance less than 3 feet having not less than a one-hour fire-resistive rating with exposure from both sides (Sheet A-0 Site Plan). Projections shall not extend to a point closer than 2 feet from the line used to determine the fire separation distance. Projections extending into the fire separation distance shall have not less than one-hour fire-resistive construction on the underside. The above provisions shall not apply to walls which are perpendicular to the line used to determine the fire separation distance as per 2018 IRC Amend Section R302.1. Revise plans with detail wall section.
3. Provide documentation and details of the architectural and electrical drawing with smoke detectors that are to be interconnected in such a manner that the actuation of one alarm will activate all of the alarms in the individual dwelling unit as per 2018 IRC Section 314.2, R314.3 and R314.4.
4. Provide documentation and details of the architectural and electrical drawings with location of carbon monoxide alarm outside of the bedroom(s), when the dwelling unit includes a fuel-fired appliance and/or has an attached garage as per 2018 IRC Section 315.2 and R315.3.
5. Revise drawings with naturally durable wood or pressure-preservative-treated wood at exterior for protection against decay and termites as per 2018 IRC Section R317.1 and R318.1.
6. Revise drawings with naturally durable wood or pressure-preservative-treated wood of framing members that rest on concrete or masonry exterior foundation walls and are less than 8 inches from the exposed ground as per 2018 IRC Section R317.1(2).
7. Revise drawings with type of fasteners for preservative-treated wood to be hot dipped zinc-coated galvanized steel, stainless steel, silicon bronze or copper as per 2018 IRC Section R317.3.
8. Revise drawings with exterior footings at least 12 inches below undisturbed ground surface as per 2018 IRC Section R403.1.4.
9. Revise drawings with anchor bolts at maximum of 6 feet on center and no fewer than two bolts per plate section for wood sole plates and sill plateson concrete floor slab, concrete, and masonry foundation/walls (other than braced wall sections) as per 2018 IRC Section R403.1.6.
10. Revise plans with roof framing details to include framing members, lumber type, grade, size, span, dimensions, spacing, anchoring and attachment information as per 2018 IRC
11. Revise drawings with 6-mil polyethylene or approved vapor retarder with joints lapped not less than 6 inches placed between the concrete slab and the base course or prepared subgrade as per 2018 IRC Section R506.2.3.
12. Uplift resistance to minimize microburst effects shall be determined by either method 1 or 2 below as per 2018 IRC Amend Section R802.11.1 Uplift resistance:
1) Design-based wind uplift criteria.
Wind uplift requirements shall be determined by using the design wind value of 115 mph within Table R802.11 for the continuous load path transmitting the uplift forces from the rafter or truss ties to the foundation.
2) Prescriptive-based wind uplift criteria.
(Please note that the requirements of this Section are in addition to those required for the structural connection of wood members).
2.1 Conventionally-framed wood or cold-formed steel structures.
All bearing wall vertical connections shall be clipped with either approved structural sheathing or approved clips to provide a continuous load path from the joist or truss through the ledger or top plate to the bottom wall plate. Where clips are used, they shall be minimum Simpson H2.5 (A34 at ledger), or equivalent load capacity, of configuration to match connection and spaced at intervals not to exceed 24". At openings, lower cripple studs do not require clipping but king/trimmer studs require double clips at bottom and upper cripples require both full clipping to header as well as header to king stud. All platform framing requires either strapping listed for the purpose or continuous sheathing over rim joist from stud to stud vertically at each floor level. All non-bearing exterior walls shall be clipped as above except that the spacing may be extended not to exceed every other stud.
2.2. Masonry or concrete structures.
If lateral design requires larger anchors or more conservative spacing, these may be used in lieu of those called out in this Section.
2.2.1. Roof bearing on wall top plate.
Top plates shall be secured to masonry or concrete walls with minimum 0.5" embedded anchor boltsspaced at intervals not to exceed 48". Each joist or truss shall be clipped to plate at bearing with minimum Simpson H2.5 or equivalent loadcapacity and of configuration to match connection. Gable end joists or trusses shall also be clipped at intervals not to exceed 48".
2.2.2. Roof bearing on wall ledger.
Joists or trusses bearing on a wall ledger shall be secured to masonry or concrete walls with minimum Simpson PAI23 purlin anchors or equal with equivalent load capacity listed for the application and embedded into wall per listing at intervals not to exceed 48”. Nonbearing roof diaphragm edges shall have the outermost joist or truss likewise anchored to the wall through blocking.
13. Provide drawings with allowable span of 7/16 APA rated sheathing (24/16) at 16 inches on center to be in compliance with APA E30 Table 34 or 37. Revise plans with sheathing details showing compliance as per 2018 IRC Section R803.2.2.
14. Provide drawings (25 snow psf + 15 dead = 40 total psf) with Allowable span as per 2018 IRC Table R802.5.1.(3)
15. Provide drawings with roof cross ventilation openingsincluding minimum of 1-inch space between the insulation and roof sheathingorprovide unvented enclosed rafter framing with air-permeable insulation (R806.5.2 climate zone 2B) as per 2018 IRC Section R806.
16. Provide drawings with a roof covering material classified as A, B or C, when the edge of the roof is less than 3 feet from property line (UL 790 or ASTM E 108) as per 2018 IRC Section R902.1. Section R802.4 & 802.5.
17. Provide drawings with roof weather protection and roof covering as per 2018 IRC Section R903, R904 and 905.
18. Provide “Compliance with the Net-Zero Energy Standard shall be deemed to comply with this code" as per 2018 IRC AmendSection N1101.4 (R102.1.1).
19. Provide documentation of the following required thermal energy values as per IECC U/R Factors:
a. Fenestration: U-factor 0.40
b. Skylights: U-factor 0.65
c. Glazed: SHGC 0.25
d. Ceiling: R-Value 38 (U-factor 0.030)
e. Wood Frame Wall: R-Value 13 (U-factor 0.084)
f. Mass Wall: R-Value 4/6 (U-factor 0.165)
g. Floor: R-Value 13 (U-factor 0.064)
h. Basement Wall: R-Value 0
i. Slab: R-Value 0
j. Crawl Space Wall: R-Value 0
20. Provide documentation of the required minimum height of rooms with sloped ceilings, at least 50 percent of the floor area of the room must have a ceiling height of at least 6 feet 8 inches and no portion of the floor area of the room may have a ceiling height of less than 5 feet as per IRC-Section AQ103.1 Minimum Ceiling Height.
21. Provide documentation and details of the footings & foundation plan for the addition as per IRC-R106.
22. Provide documentation and details of the required wall bracing details and method, including but not limited to the garage as per IRC-R602.10.
23. Provide documentation and details of the required FASTENING SCHEDULE as per TABLE R602.3(1).
24. Provide documentation and details of the required flashings shall be installed in a manner that prevents moisture from entering the wall and roof through joints in copings, through moisture permeable materials and at intersections with parapet walls and other penetrations through the roof plane as per R903.2.
25. Provide documentation and details of the required Roof decks shall be covered with approved roof coverings secured to the building or structure in accordance with the provisions of this chapter. Roof assemblies shall be designed and installed in accordance with this code and the approved manufacturer's instructions such that the roof assembly shall serve to protect the building or structure as per R903.1.
26. Provide documentation and details of the required Geotechnical Evaluation. In lieu of a complete geotechnical evaluation the load-bearing values in Table R401.4.1 shall be assumed. A complete geotechnical evaluation is required for presumptive load-bearing values greater than 1500 pounds per square foot as per R401.4.1.
27. Provide documentation and details of the required structural beams & headers throughout plan as per R106.1.
28. Provide documentation and details of the required Drainage.
All drainage shall conform to the requirements of Chapter 32A of the Phoenix City Code as per R401.3.
a. All drainage facilities shall comply with the City of Phoenix Stormwater Policies and Standards Manual.
b. Geotechnical reports certifying the compaction or acceptability of all fills shall be required except as exempted by Section 32A-15.C.
c. Erosion prevention. Adequate provision shall be made to prevent surface waters from damaging the face of an excavation or fill. All slopes shall be protected from surface water runoff from above by berms, swales, walls, stabilized slope treatment, or other protection as approved by the Planning and Development Director.
29. Provide required inspections as per City of Tucson Development Services Department.
30. Sheet A-2 Elevations shows stucco. Provide documentation and details of the required Lath and lath attachments shall be of corrosion-resistant materials. Expanded metal or woven wire lath shall be attached with 11/2-inch-long, 11-gage nails having a 7/16-inch head, or 7/8-inch-long, 16-gage staples, spaced not more than 6 inches or as otherwise approved as per R703.7.1.
31. Sheet A-2 Elevations shows stucco. Provide documentation and details of the required Plaster. Plastering with cement plaster shall be in accordance with ASTM C926. Plaster shall be not less than three coats where applied over metal lath or wire lath and shall be not less than two coats where applied over masonry, concrete, pressure-preservative-treated wood or decay-resistant wood as specified in Section R317.1 or gypsum backing. If the plaster surface is completely covered by veneer or other facing material or is completely concealed, plaster application need be only two coats, provided the total thickness is as set forth in Table R702.1(1).
On wood-frame construction with an on-grade floor slab system, exterior plaster shall be applied to cover, but not extend below, lath, paper and screed. The proportion of aggregate to cementitious materials shall be as set forth in Table R702.1(3) as per IRC-R703.7.2.
32. Sheet A-2 Elevations shows stucco. Exterior Insulation and Finish System (EIFS) With Drainage as per IRC-R703.9.2.
EIFS with drainage shall comply with the following:
ASTM E2568.
EIFS with drainage shall be required over all wall assemblies with the exception of substrates of concrete or masonry wall assemblies.
EIFS with drainage shall have an average minimum drainage efficiency of 90 percent when tested in accordance with ASTM E2273.
The water-resistive barrier shall comply with Section R703.2 or ASTM E2570.
The water-resistive barrier shall be applied between the EIFS and the wall sheathing.
Flashing of EIFS with drainage shall be provided in accordance with the requirements of Section R703.4.
EIFS with drainage shall be installed in accordance with the manufacturer's instructions.
EIFS with drainage shall terminate not less than 6 inches (152 mm) above the finished ground level.
Decorative trim shall not be face-nailed through the EIFS with drainage.


MECHANICAL REVIEW COMMENTS:
Denied
Please make corrections and resubmit. Resubmittal shall include a response letter. All code references are to the IRC edition as adopted by Tucson, AR & City of Tucson Amendments to the 2018 IRC unless otherwise noted. Recommend clouding changes to speed up the rereview.
1. Provide documentation and details of the heating and cooling facilities capable of Required heating. Exception: Spaces able to maintain 60ºF at a point 3 feet above the floor and 2 feet from exterior walls in all habitable rooms over a 48 hour period as demonstrated by Section N1105 Simulated Performance Alternative as per City of Tucson Amendments to the 2018 IRC & Section IRC-R303.10 Required heating.
2. The building official or other authority having jurisdiction shall be permitted to deem a national, state or local energyefficiency program to exceed the energy efficiency required by this code. Buildings approved in writing by such an energyefficiency program shall be considered to be in compliance with this code. The requirements identified as "mandatory" in this chapter, as applicable, shall be met as per IRC-Section N1101.4 (R102.1.1) Above code programs. “Compliance with the Net-Zero Energy Standard shall be deemed to comply with this code.”
3. Provide the required airleakage testing.
The building or dwelling unit shall be tested and verified as having an air leakage rate of not exceeding five air changes per hour in Climate Zones 1 and 2, and three air changes per hour in Climate Zones 3 through 8. Testing shall be conducted in accordance with RESNET/ICC 380, ASTM E779 or ASTM E1827 and reported at a pressure of 0.2 inch w.g. (50 Pascals).
Testing shall be conducted by individuals holding current certification for such testing from Residential Energy Services Network (RESNET), Building Performance Institute (BPI) or other approved agencies as per City of Tucson Amendments to the 2018 IRC. A written report of the results of the test shall be signed by the party conducting the test and provided to the building official. Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
During testing:
a. Exterior windows and doors, fireplace and stove doors shall be closed, but not sealed, beyond the intended weatherstripping or other infiltration control measures.
b. Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed beyond intended infiltration control measures.
c. Interior doors, where installed at the time of the test, shall be open.
d. Exterior or interior terminations for continuous ventilation systems shall be sealed.
e. Heating and cooling systems, where installed at the time of the test, shall be turned off.
f. Supply and return registers, where installed at the time of the test, shall be fully open.
4. Provide documentation and details of the required Condensate Disposal.
Condensate from cooling coils and evaporators shall be conveyed from the drain pan outlet to an approved place of disposal. Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than 1/8 unit vertical in 12 units horizontal (1-percent slope). Condensate shall not discharge into a street, alley or other area where it would cause a nuisance as per City of Tucson Amendments to the 2018 IRC & IRC-Section M1411.3 Condensate disposal. Condensate disposal shall be allowed to terminate as follows:
a. Into an approved fixture tailpiece, funnel drain, waste air gap fitting, floor sink, slop sink and laundry tray.
b. At or below grade outside the building in an area capable of absorbing the condensate flow without surface drainage.
c. Over roof drains or gutters or downspouts that connect to drainage pipes, provided they terminate at or above grade in an area capable of absorbing the condensate flow without surface drainage.
5. If Evaporative cooling systems are provided with a recirculating water system. Any bleed off rate used by the system shall be limited to that recommended by the manufacturer. Once-through evaporative cooling systems using potable water shall not be permitted as per City of Tucson Amendments to the 2018 IRC & IRC-Section M1413.2 Water conservation.
6. Provide documentation and details of the required mechanical (HVAC) plans showing the following components of the air distribution system:
(1) Airflow (CFM) at each diffuser and register.
(2)Sizes of all diffusers, registers, and grilles.
(3) Sizes of all sections of ductwork.
(4)Total supply airflow capacity (CFM) of HVAC equipment.
(5) Total amount of outside air (CFM) introduced into the HVAC equipment.
(6)Total heating capacity of the equipment (include both the input and output ratings).
(7)Total and sensible cooling capacity of the equipment.
(8) All vent sizes and details of venting, including the termination points outside.
(9) Show all control devices, sensors, and related accessories.
(10) All exhaust fans schedule and duct sizes and details of routing, including the termination points outside as per IMC-106.3.1.
7. Provide documentation and details of the required ventilation requirements for each space as per T403.3.1.1 Minimum Ventilation Rates.
8. Provide documentation and details for Structural Attachment of Hangers and anchors required to be attached to the building construction in an approved manner as per IMC 305.3.
9. Provide all required safeguards for demolition & construction including but not limited to Storage and placement, required exits, fire protection devices, manner of removal, Construction documents, Schedule of Demolition, Means of egress, Service utility connections discontinued and capped, Sanitary facilities during construction, Protection required, Obstructions & Fire Extinguisher(s).
10. If Exhaust Outlets are included in the mechanical provisions, provide documentation and details of Location of Exhaust Outlets as required per IMC 501.3.1:
a. For ducts conveying explosive or flammable vapors, fumes or dusts: 30 feet from lot lines; 10 feet from operable openings into buildings; 6 feet from exterior walls and roofs; 30 feet from combustible walls and operable openings into buildings which are in the direction of the exhaust discharge; and 10 feet above adjoining grade.
b. For other product-conveying outlets: 10 feet from the lot lines; 3 feet from exterior walls and roofs; 10 feet from operable openings into buildings; and 10 feet above adjoining grade.
c. For all environmental air exhaust: 3 feet from a lot line that adjoins the public way or 10 feet above the sidewalk or finished grade of the public way; 3 feet from all other lot lines; 3 feet from operable openings into buildings for all occupancies other than Group U, and 10 feet from mechanical air intakes. Such exhaust shall not be considered hazardous or noxious.
11. Provide required inspections as per City of Tucson Development Services Department.


ELECTRICAL REVIEW COMMENTS
Denied
Please make corrections and resubmit. Resubmittal shall include a response letter. All code references are to the IRC edition as adopted by Tucson, AR & City of Tucson Amendments to the 2018 IRC & NEC unless otherwise noted. Recommend clouding changes to speed up the rereview.
1. Provide means to disconnect all conductors in building from the service entrance conductors in a readily accessible location & mark each service disconnect as per Section 230.70(B) Marking. The markings shall be of sufficient durability to withstand the environment involved. Identifying labels required for disconnecting means shall have engraved or raised letters and be secured by screws or rivets (plastic tape shall not be considered durable material) as per Section 230.70(B) & City of Tucson Amendments to the 2018 IRC.
2. Revise electrical drawings with location of main service panel including working space, clearances and access as per 2018 IRC Section E3405 and E3606.
3. Revise electrical drawings with location of service grounding, bonding and conductor details as per 2018 IRC Section E3603, E3607, E3608, E3609, E3610 and E3611.
4. Dishwasher and garbage disposer branch circuits – Dwelling units. In residential occupancies, dishwasher and garbage disposer may be on the same 20-ampere branch circuit as per Section E3703.8.
5. Revise electrical drawing with dishwasher and garbage disposer on the same 20-ampere branch circuit (15 amp shown) as per 2018 IRC Added Section E3703.8.
6. Indicate the size & location of Electrical Panel as per IRC E4101.5.
7. Provide electrical plan showing the following components of the electrical distribution system, as they apply to this project as per IRC.
8. Provide electrical Power Riser Diagram, including sizes of all feeders as per IRC.
9. Provide location, size, and type of the service entrance conductors as per IRC.
10. Provide location and ratings of all distribution panels between the service entrance and the new or modified panels used for this project as per IRC.
11. Provide an electrical floor plan that includes all the home runs to the panels that feed all devices and electrical equipment within the scope of work for this project as per IRC.
12. Provide Panel directory (schedule) of all panelboards directly used for this project-new or existing-as well those that might be feeding them as per IRC.
13. Provide load calculations for all panelboards-existing or new if connected with this project as per IRC.
14. Provide Service or transformer grounding detail that includes the size of the grounding electrode conductors and the available grounding electrodes used as per IRC.
15. Provide single line diagram; show electrical panel load schedules, conduit and conductor sizes and ground electrode detail as per IRC.
16. Provide service load calculation. (230.42, 93.0207(n)).
17. Provide properly sized grounding electrode conductors for the service(s). (250.20, 250.26, 250.66).
18. Where a receptacle outlet is supplied by a branch circuit that required arc-fault circuit interrupter protection as specified elsewhere in this code, a replacement receptacle at this outlet shall be one of the following: (406.4(D)(4))
a) A listed outlet branch circuit type arc-fault circuit interrupter receptacle.
b) A receptacle protected by a listed outlet branch circuit type arc-fault circuit interrupter type receptacle.
c) A receptacle protected by a listed combination type arc-fault circuit interrupt type circuit breaker.
19. A panelboard shall be protected by an overcurrent protective device having a rating not greater than that of the panelboard. This overcurrent protective device shall be located within or at any point on the supply side of the panelboard. (408.36).
20. Provide Ground-Fault Circuit-Interruption for (A) Dwelling Units (2) Garages as per 210.8.
21. Provide Arc-Fault Circuit Interrupter (AFCI) Protection for Family & Home Theatre as per 210.12 (NEC).
22. Provide Dwelling Unit Receptacle Outlets for Family & Home Theatre spaced 12 ft. on center as per 210.52(A)(1)(NEC).
23. Provide required inspections as per City of Tucson Development Services Department.


PLUMBING REVIEW COMMENTS:
Denied
Please make corrections and resubmit. Resubmittal shall include a response letter. All code references are to the IRC edition as adopted by Tucson, AR & City of Tucson Amendments to the 2018 IRC unless otherwise noted. Recommend clouding changes to speed up the rereview.
1. Provide documentation and details of the required Water conservation & Connections to Drainage System. Plumbing fixtures, drains, appurtenances and appliances used to receive or discharge liquid wastes or sewage shall be directly connected to the sanitary drainage system of the building or premises, in accordance with the requirements of this code. This section shall not be construed to prevent indirect waste connections where required by the code.All new residential dwelling units shall include piping to allow separate discharge of graywater for direct irrigation in accordance with Table 2601.2. When feasible, all gray water discharge piping shall be installed to allow for gravity distribution as per City of Tucson Amendments to the 2018 IRC.
2. Provide documentation and details of all gray water systems shall be designed and operated according to the provisions of the applicable permit authorized by ADEQ under the Arizona Administrative Code, Title 18, Chapter 9 as per Section P2601.2.1 Gray water piping & City of Tucson Amendments to the 2018 IRC.
3. Provide documentation and details of Subsoil drains conforming to Table P3302.1 & min. 4 inches in diameter. Where the building is subject to backwater, the subsoil drain shall be protected by an accessibly located backwater valve. Subsoil drains shall discharge to a trapped area drain, sump, dry well or approved location above ground. The subsoil sump shall not be required to have either a gas-tight cover or a vent. The sump and pumping system shall comply with Section P3303 as per IRC-P3302.1 Subsoil Drains.
4. Provide documentation and details of the required Drainage.
All drainage shall conform to the requirements of Chapter 32A of the Phoenix City Code as per R401.3.
a. All drainage facilities shall comply with the City of Phoenix Stormwater Policies and Standards Manual.
b. Geotechnical reports certifying the compaction or acceptability of all fills shall be required except as exempted by Section 32A-15.C.
c. Erosion prevention. Adequate provision shall be made to prevent surface waters from damaging the face of an excavation or fill. All slopes shall be protected from surface water runoff from above by berms, swales, walls, stabilized slope treatment, or other protection as approved by the Planning and Development Director.
5. If natural gas is utilized for heating the Family & Theatre addition, provide documentation and details of the required Identification of each length of pipe and tubing and each pipe fitting, utilized in a fuel gas system, shall bear the identification of the manufacturer as per IRC-G2412.5.
6. If natural gas is utilized for heating the Family & Theatre addition, provide documentation and details of the required Access to Shutoff Valves.
Shutoff valves shall be located in places so as to provide access for operation and shall be installed so as to be protected from damage as per IRC-G2420.
7. If natural gas is utilized for heating the Family & Theatre addition, provide documentation and details of the required Identification of Shutoff Valves.
Each house line shutoff valve shall be plainly marked with an identification tag attached by the installer so that the piping systems supplied by such valves are readily identified as per IRC-G2420.5.3.
8. If natural gas is utilized for heating the Family & Theatre addition, provide documentation and details of the required appliance Shutoff Valves shall be Located Within Same Room as the appliance. The shutoff valve shall be within 6 feet of the appliance, and shall be installed upstream of the union, connector or quick disconnect device it serves as per IRCG2420.5.3.
9. If natural gas is utilized for heating the Family & Theatre addition, provide documentation and details of the required Interval of Support of Piping not exceeding the spacing specified in Table 415.1. Spacing of supports for CSST shall be in accordance with the CSST manufacturer's instructions as per IRC-G2418.
10. If natural gas is utilized for heating the Family & Theatre addition, provide documentation and details of the Venting Systems Required for all appliances by detailed drawings specifying but not limited to size, installation, supports, clearances, fireblocking, cleanouts, listing/ labeling, roof penetration, termination, minimum height & marking as per IRC-Chapt. 24.
11. If natural gas is utilized for heating the Family & Theatre addition, provide documentation and details of the specific appliances identified herein to meet the requirements for the approval, design, installation, construction, alteration maintenance, and repair of the appliances and equipment specifically noted as per Chapter 24 of IRC.
12. If natural gas is utilized for heating the Family & Theatre addition, provide documentation and details of the Piping systems shall be of such size and so installed as to provide a supply of gas sufficient to meet the maximum demand and supply gas to each appliance inlet at not less than the minimum supply pressure required by the appliance as per Section G2413 (402) Pipe Sizing.
13. If natural gas is utilized for heating the Family & Theatre addition, provide documentation and details of the Design and Construction of the venting of Appliances required to be vented shall be connected to a venting system designed and installed in accordance with the provisions of Sections G2427.4 through G2427.16 as per IRC-G2427.3.2 (503.3.2).
14. Provide required inspections as per City of Tucson Development Services Department.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
10/04/2022 JCARLTO1 NPPO REVIEW Passed