Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM06891
Parcel: 12701005D

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM06891
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2022 SHASEMA1 ENGINEERING REVIEW Passed
09/12/2022 WBERGER1 ZONING REVIEW Approved
09/12/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/16/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM06891

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
N/A


BUILDING REVIEW COMMENTS:
Denied
1. The occupant load is calculated incorrectly. Beyond permant fixed seating, there is no concept of seat counting in the IBC. A space by space occupant load approach is appropriate. Additionally, it appears that concentrated business use is present. Provided corrected occupant load calculations in accordance with Section 1004.3, Table 1004.5 and Section 1004.8.
2. Provide the area of the scope of work.


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Denied
1. Provide the updated locations of new exit lighting in accordance with Section 1013.
2. Provide the updated locations of new egress illumination in accordance with Section 1008.


PLUMBING REVIEW COMMENTS:
Approved



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
09/22/2022 JVINCEN1 FIRE REVIEW Approved
10/04/2022 ROBERT SHERRY WATER REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
10/05/2022 NGARCIA3 OUT TO CUSTOMER Completed