Permit Number: T22CM06879
Parcel: 12107001A

Review Status: Active

Review Details: 3RD PARTY REVIEW - COMMERCIAL TI

Permit Number - T22CM06879
Review Name: 3RD PARTY REVIEW - COMMERCIAL TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2022 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Active
09/07/2022 VFLORES1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change Please contact Pima County Addressing to have suite # added into the system Phone #:520-724-9512 Email: addressing@pima.gov
09/20/2022 WILDAN 3RD PARTY REVIEW-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM06879

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

BUILDING REVIEW COMMENTS:
Denied
Sheet A0.01, Table 2902.1; Provide total occupant load for entire suite. TImeans of egress identifies TIwork is addition to existing suite. DMA
Sheet A0.01; Provide overall occupant load calc for combined existing suite and expansion suite. DMA
Sheet A1.0; Door swing cannot reduce the required clear width of the corridor by less than 50% during course of the swing. DMA
Sheet A1.0; Identify accessible seating at table on plans. DMA
Sheet A1.0; Door identified as exit in means of egress. Provide means of egress plans for entire suite. Review performed assuming submittal is an addition to exiting suite. DMA
Sheet A1.01; Fireblocking will be field verified. DMA
Sheet A6.01; Verify and add to notes, all hardware will comply with ADA. DMA
Sheet M1.0; Provide reflected cieling plan and add detail for cieling grid framing, luminaires supports, wiring, etc... DMA



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
09/20/2022 DBENOIT1 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Reqs Change
09/21/2022 SSHIELD1 ENGINEERING REVIEW Passed
09/21/2022 STEVE SHIELDS ZONING REVIEW Approved
09/30/2022 JVINCEN1 FIRE REVIEW Reqs Change -Resolve building comments.
-Indicate in the code analysis if building has a fire alarm. Your deferred submittals currently include fire alarm.

john.vincent@tucsonaz.gov
5203495581
10/03/2022 ROBERT SHERRY WATER REVIEW Completed