Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T22CM06869
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/07/2022 | SHASEMA1 | ENGINEERING | REVIEW | Passed | |
| 09/12/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review Section PROJECT: T22CM06869 1609 E Seneca St. – NR-1 Attached Porch Addition (1st Review) TRANSMITTAL: September 12, 2022 COMMENTS: the following comments are relative to an application for NPZ Review (UDC 5.10.3). This site is located in the NR-1 zone (UDC 5.10.3). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 – 9. 1. Provide an elevation look north of the front of the house so that Design Review can verify that the proposed additions are not visible from the street, contact Nick Martell if you have any questions at: Nicholas.Martell@tucsonaz.gov. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
| 09/26/2022 | JCARLTO1 | NPPO | REVIEW | Passed | |
| 09/27/2022 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | Provide all dimensions for determining the point load at beam to existing beam connection. A 4x8 DF#2 existing beam appears as undersized for accepting the new live and dead loads. |