| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/06/2022 | RPARSON1 | OIP | REVIEW | Completed | |
| 09/20/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM06830 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved Engineering calculations and letter approved BUILDING REVIEW COMMENTS: Approved Installation of new PV System with 17 modules and associated equipment MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Denied 1. Electrical diagram indicates a back feed breaker on a 200 amp panel. Yet labels indicate a derated main breaker and possibly supply side taps with warnings on E1 and E2. Please clarify labeling/warnings for this system. R301.1 PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/20/2022 | VVERA1 | OUT TO CUSTOMER | Completed |