| 09/06/2022 | RPARSON1 | OIP | REVIEW | Completed | |
| 09/20/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM06829 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Denied 1. Provide an up-lift calculation demonstrating the wind load supporting capability based upon a a v-ult wind speed of 115 MPH per AHJ amended code R301.1. MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Denied 1. Place the backfeed breaker at the furthest position away from the main breaker, NEC 705.12(B)(2)(3)(b). PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |