Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 The electrical plans are not complete. Provide detailed information, notes, to show the entire scope of work for this phase of the project.

2 In relation to the electrical line diagram submitted; Show complete panel schedules for all proposed new panels. Include the DP panels, and correlating load calculations.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/28/2022 NGARCIA3 OUT TO CUSTOMER Completed