Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM06787
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/06/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. Could not verify the following electrical code compliance by looking at the photos submitted. 1 Verify approved ceiling fan boxes were installed for the ceiling fans. 2 The permit application stated that the receptacles and GFI’s were replaced. Verify that the receptacles were replaced with Tamper Resistant and Arc Fault as required per NEC art 406.4D. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
| 10/07/2022 | JGARCIA1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1. Provide a complete scope of all work including any structural repairs required. 2. Verify all smoke detectors have been replaced. Ref; 2018 IBC sec 107.2.1, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/07/2022 | VVERA1 | OUT TO CUSTOMER | Completed |