Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM06773
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/19/2022 | WBERGER1 | ZONING | REVIEW | Approved | |
| 09/19/2022 | SHASEMA1 | ENGINEERING | REVIEW | Passed | |
| 09/19/2022 | WBERGER1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/20/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 09/20/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 09/20/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 09/23/2022 | PSHELTO1 | FIRE | REVIEW | Approved | |
| 09/27/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/18/2022 | WILDAN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Activity Number: T22CM06773 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. Denied Sheet A4 What is the weight of this water heater Filled? Sheet A4 Provide Accessible Path of Travel required exits. Show details for landing at exit doors. Show Location of Accessible seating per ADAAG. Sheet A4 Provide expanded view of required ADAAG Restrooms. Provide details of all fixture layouts. Sheet M1 Provide structural details for all new roof openings. Show existing roof was designed to carry additional weight of new equipment. If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |