Permit Number: T22CM06767
Parcel: 10711014A

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM06767
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/28/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the room number for the equipment installation. The approved building plans label the location as kitchen 104, not 107. Reference: Section 107.2.1, IBC 2018.
2. Correct the equipment schedule for EQ-07 to reflect a total natural gas load of 227,000 BTUH.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/28/2022 NGARCIA3 OUT TO CUSTOMER Completed