Permit Number: T22CM06680
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM06680
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2022 SHASEMA1 ENGINEERING REVIEW Passed
09/08/2022 PSHELTO1 FIRE REVIEW Approved
09/12/2022 WBERGER1 ZONING REVIEW Passed
10/18/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM06680

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Denied
Sheet A103c Add the following sections from IBC 1010.1.9.8.1 3.Delayed systems shall have the capability of being deactivated at the Fire Command Center or other approved locations. 6. A sign shall be provided on the door and shall be located above and within 12 inches of the door exit hardware. 6.2 For doors that swing the opposite direction of travel, the sign shall read: PULL UNTIL ALARM SOUNDS.DOOR CAN BE OPENED IN 15 SECONDS. 7. Emergency Lighting shall br provided on the egress side of the door.
Sheet A103c Plan shall be signed and sealed by an Arizona Registrant
Sheet A103c Provide SF of Area Provide building Construction TYPE



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
10/19/2022 NGARCIA3 OUT TO CUSTOMER Completed