Permit Number: T22CM06679
Parcel: 11206431B

Address:
2425 N TUCSON BL

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM06679
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2022 SHASEMA1 ENGINEERING REVIEW Passed
09/13/2022 STEVE SHIELDS ZONING REVIEW Approved
09/13/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change An electric conveyor oven is classified as a medium duty appliance and, unless is listed under UL 710B (factory-built, commercial cooking, recirculating system), it will require the installation of a Type I hood. Reference: Section 507.1, IMC 2018.
09/13/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/13/2022 ROBERT SHERRY WATER REVIEW Completed
09/13/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/15/2022 PSHELTO1 FIRE REVIEW Reqs Change ADDRESS MECHANICAL COMMENTS

PATRICIA SHELTON
PATRICIA.SHELTON@TUCSONAZ.GOV
520.837.7082
09/27/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comment.
There are 2 panels identified as 'Panel L2' on the power plan. Please clarify.
2018 IBC section 107.2, 2017 NEC
10/18/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM06679

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Denied
Sheet G1.0 Provide actual SF leased area for Pasta La Vista
Sheet A1 Provide expanded view of restrooms showing compliance with ADAAG and IBC Chapter 11.
Sheet A1 Provide details of Order Counter per ADAAG 34-36 inch high.
Sheet A1 Provide path of travel to Accessible parking and the public way.
Sheet A1 Provide reflected ceiling plan showing required tiles in Kitchen. Provide equipment or storage racks in Dry STG Area
Sheet A1 Provide list of items being cooked to determine if A type 1 or type 2 hood is required.
Sheet A1 Provide manufactures cut sheet for Pizza Conveyor, to determine if any hood is required.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov