Permit Number: T22CM06671
Parcel: 12009309D

Address:
4775 S 3RD AV

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM06671
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2022 SHASEMA1 ENGINEERING REVIEW Approved
09/14/2022 STEVE SHIELDS ZONING REVIEW Approved
10/06/2022 JPEELDA1 FIRE REVIEW Reqs Change The operation in the building that is driving the COFO change is the piping of the flammable liquids into the building at greater than 15 psi. Chapter 2 Definitions of the H2 Occupancy. It is not the paint booth that is causing this issue, it only requires an operational permit and the owner has already obtained from TFD. As drawn and designed currently the entire building is classified as a H2 non separated use. Drawings shall be re-drawn to meet all the requirements for an H2. Further questions you may also call Tim Gard 520-837-7031 or email him @ Tim.Gard@Tucsonaz.gov

Questions:
Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner
Jennifer.Peel-Davis@Tucsonaz.gov
Desk: 520-837-7033
10/18/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM06671

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Denied
Sheet G000 Provide Site Plan showing Accessible Parking. Show Accessible Path of Travel to Required Accessible Entrances and Exits.
Sheet G000 This is a full TI plan. Provide MPE plans. Additional comments may follow on 2nd review.
Sheet G111 Provide wall key Plan. Show Details locations on plan. Identify rated doors and ratings required.
Sheet G111 Provide expanded plan showing ADA Restrooms. Provide High Low Drinking Fountain per ADAAG and IBC Chapter ii.
Sheet A500 Provide note all door hardware complies with ADAAG.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
10/19/2022 NGARCIA3 OUT TO CUSTOMER Completed