Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM06653
Parcel: 117200100

Address:
165 W ALAMEDA ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM06653
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2022 SSHIELD1 ENGINEERING REVIEW Passed
09/14/2022 STEVE SHIELDS ZONING REVIEW Approved
09/16/2022 JVINCEN1 FIRE REVIEW Approved
09/22/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Reference: Electrical plans.

1 Show the fountain lighting on the plan as noted on plan sheet E1.1, Keynote #4, and the panel schedule branch circuit #7. If the fountain lighting is to be installed by others under a separate permit, please indicate this with a note on the electrical plans.

2 Provide full compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the fountain lighting as required per section 104.1 OLC (if applicable).

3 Verify wiring methods, grounding, bonding, GFI protection complies where applicable per NEC art 680.50.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 City of Tucson/Pima County Outdoor Lighting Code, (OLC).
09/22/2022 WILDAN BUILDING-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/22/2022 VVERA1 OUT TO CUSTOMER Completed