Permit Number: T22CM06582
Parcel: 113081980

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM06582
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2022 SHASEMA1 ENGINEERING REVIEW Passed
09/06/2022 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T22CM06582
1121 E Hedrick Dr – R-2
Convert Carport to dwelling unit (1st Review)

TRANSMITTAL DATE: September 6, 2022

Provided a detail comment response letter with your submittal that clearly shows how you have addressed all comments with your next submittal.

This site is located in the R-2 zone (UDC 4.7.9). A Multifamily Development is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10

1. Per UDC TABLE 6.3-2.A: DIMENSIONAL STANDARDS FOR THE R-1, R-2, R-3, MH-1, & MH-2 ZONES, R-2 Zone the allowed density for a multi-family development is 15 units per acre. Based on a lot size of 10,787 square feet, as shown on the plan, converts to 0.25 acres. 0.25 x 15 = 3.75 or 3 units allowed on this site. At a minimum a Board of Adjustment for Variance will need to be submitted and approved for the 4th dwelling unit on this site. Most likely a rezoning to a R-3 zone will be required. Board of Adjustment application/requirements can be found at: https://www.tucsonaz.gov/files/pdsd/codes/Zoning_Administration_Application_BA_fillable.pdf. The Board of Adjustment is a separate submittal from this building plan and is submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. Contact for the Board of Adjustment is Mark Castro at Mark.Castro@tucsonaz.gov. Rezoning application/requirements can be found at: https://www.tucsonaz.gov/pdsd/all-application-forms-submittal-requirements. Rezoning is a separate submittal from this building plan and is submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Entitlements”. Contact for the Rezoning process is John Beall at John.Beall@tucsonaz.gov. The above must be addressed prior to approval of this building permit.

2. As you are proposing 4 dwelling units on a single site this site is considered a non-residential project and will require a Development Package meeting the requirements of Administrative Manual (AM) 2-06. AM 2-06 can be found at: https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-4930, and must be submitted and approved prior to approval of this building plan. The DP is a separate submittal from the building plans and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using Submission Type “Site Review”.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
09/12/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T22CM06582
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

Upon Zoning approval provide a complete plan set showing 2018 IRC compliance including a wall and foundation detail showing materials, locations, sizing and fastening, electrical, plumbing, heating and cooling.

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

Each dwelling unit with kitchen requires a separate Pima County assigned street address, R319. Notate each dwelling address on the site plan (or remove cooking appliances).

GENERAL COMMENTS (for dwelling with kitchen):

1. Show compliance with the Inclusive Home Design Ordinance adopted by the City of Tucson Ordinance #10463 on 10/16/2007. Notate accessible route, minimum door width, changes in floor elevation, door hardware, electrical outlet reach range, grab bar reinforcement, etc.

SITE PLAN:

1. Show the location and size of buildings, utility meters and gas, water, electric and sewer or septic lines from property line to building, R106.1.1. Identify the utility lines requiring upgrade or replacement.
2. Show a street address for each dwelling on the site plan, R319.

PLANS:

1. Show a maximum ½” floor elevation changes at a notated accessible route entrance on the floor plan, R106.1.1. Include the threshold condition at the vehicle doorway or an exterior hinged door when the garage is used for the accessible route.
2. Notate a cool (white) roof finish as required by the ADU provisions.
3. Show the proposed structure with one-hour fire-resistive wall construction parallel with the property line in compliance with IBC Table 721.1(2) or show a clear 3’ fire separation distance between the property line and the structure.
4. Roof projections extending into the 3-foot fire separation distance require not less than one-hour fire-resistive construction on the underside, R302.1 (City of Tucson Amended). The fire protected overhang may not extend closer than 24” from the property line.

SECTIONS - DETAILS:

1. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation or need for providing air-impermeable rigid insulation at the roof, R806.
2. Show an unvented roof assembly with all insulation at the roof including an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing as part of the total R-38 insulation requirement, R806.5 or show the attic vent opening size using 1 to 150 of attic area with insulation at the ceiling in compliance with R806.2.

PLUMBING PLANS:

1. Tucson Water Department limits flow rates for each water meter size in compliance with P2903.7. Show an appropriate yard pipe bypassing the existing dwelling and the water meter size.
2. Provide a complete plumbing plan.

MECHANICAL PLANS:

1. Provide a complete mechanical plan.
2. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation, or controlled exhaust with a calculated airflow rate, R303.4; N1103.6 & M1505.4. Show the system and appropriate flow rate setting on the plans. A one bedroom dwelling under 1501 SF requires a 30 CFM continuous setting.
3. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D. Notate if the mechanical plans if system calculations will be provided by deferred submittal.

ELECTRICAL PLANS:

1. TEP may require the service panel for the property at the closest building to the service transformer. A service line change or a new meter location must be coordinated with TEP for approval. Show an underground feeder from a metered service panel to the more distant dwelling.
2. Update the Riser Diagram for the close dwelling and the feeder size to the detached dwelling panel per TEP coordination, NEC 225.30 and E3403.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
(520) 837-4912 PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review
09/26/2022 JCARLTO1 NPPO REVIEW Passed