Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM06564
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2022 SHASEMA1 ENGINEERING REVIEW Passed
08/31/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Show braced wall panel compliance for narrow framed walls with a garage door opening, Table R602.10.5. For prescriptive braced wall structures show a portal frame with hold-downs PFH method, Figure R602.10.6.2, or a portal frame at garage door PFG method, Figure R602.10.6.3.
09/12/2022 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T22CM06564
9243 E Calle Cascada – R-1
Garage Extension (1st Review)

TRANSMITTAL DATE: August 31, 2022

Provided a detail comment response letter with your submittal that clearly shows how you have addressed all comments with your next submittal.

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 – 9.

1. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf,
a. The plot plan shall be drawing at an engineering scale, 1” = 10’, 1” = 20’ etc.
b. Provide parcel dimensions on the plot plan.
c. Provide the zoning for this parcel and all adjacent parcels on the plot plan. The Zoning should be listed as R-1.
d. Provide a lot coverage calculation on the plans.
e. Show all utility lines on the plot plan.
f. Provide a dimension from the centerline of Calle Cascada. to the street side of curb and from the street side of curb to the property line. The dimension from centerline to curb is 19’-0” and from curb to property line is 11’-0”, reference paving plan I-71-030 found at: https://www.tucsonaz.gov/apps/maps-and-records/construction-plans/details/I-71-030.

2. Show all structures on the plot plan along with perimeter yard setbacks, this shall include any sheds, shade sails, etc.

Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A.

3. The minimum setback to the front street perimeter property line is the greater of twenty (20) feet, or one and one-half (1 ½) the height of the proposed wall ((UDC 6.4.5.C.1.a). If the proposed garage extension does not meet the require front street perimeter yard setback a Board of Adjustment for Variance will be required to reduce the front street perimeter yard setback.

Board of Adjustment application/requirements can be found at: https://www.tucsonaz.gov/files/pdsd/codes/Zoning_Administration_Application_BA_fillable.pdf. The Board of Adjustment is a separate submittal from this building plan and is submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. Contact of the Board of Adjustment is Mark Castro at Mark.Castro@tucsonaz.gov.
If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
09/23/2022 AWARNER1 NPPO REVIEW Approved Protect existing native plants during construction.