Permit Number: T22CM06556
Parcel: 11901042B

Address:
200 E BENSON HY

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T22CM06556
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2022 PSHELTO1 FIRE REVIEW Approved
09/12/2022 SSHIELD1 ENGINEERING REVIEW Passed
09/12/2022 PETER MCLAUGHLIN PLANNING-CITY HALL REVIEW Approved
09/12/2022 PETER MCLAUGHLIN ZONING REVIEW Completed
09/14/2022 DBENOIT1 BUILDING-COMMERCIAL REVIEW Completed
09/20/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Ref; Electrical line diagram.

Indicate the rating in amps for the OCPD in the generator protecting the feeders to the transfer switch.

What does the encircled letter G represent next to the generator OCPD? Indicate this on the electrical plan.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/21/2022 NGARCIA3 OUT TO CUSTOMER Completed