Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM06553
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/24/2022 | RPARSON1 | OIP | REVIEW | Completed | |
| 08/30/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM06553 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied 1. Provide a lag bolt connection uplift calculation demonstrating the wind load supporting capability. R301.1 2. Provide sufficient standoffs for achieving a point load calculation under 45 lbs. Show Calculation R301.1 BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/30/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |