Permit Number: T22CM06538
Parcel: 131111590

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM06538
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2022 SHASEMA1 ENGINEERING REVIEW Passed
08/30/2022 PAUL CAMARENA ZONING REVIEW Approved
08/30/2022 PCAMARE1 NPPO REVIEW Passed
08/31/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change 1. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm in each bedroom and outside in the immediate vicinity.

2. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6.

3. Protect new and extended branch circuits with combination type arc-fault circuit interrupters, or an AFCI type receptacle at the first outlet on the branch circuit, E3902.17.