Permit Number: T22CM06526
Parcel: 136244570

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM06526
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2022 SHASEMA1 ENGINEERING REVIEW Passed
09/08/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the occupant load calculations to account for the fixed seats in the dining area (16 seats per sheet A4) and the order area (standing space at 5 square feet per person)in addition to the 2 occupants in the kitchen. Revise the number of required plumbing fixtures for the building accordingly. Reference: Sections 1004.5, 1004.6, and 2902.1, IBC 2018
09/08/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
09/08/2022 ROBERT SHERRY WATER REVIEW Completed
09/09/2022 STEVE SHIELDS ZONING REVIEW Approved
09/09/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/14/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Show location and provide power and disconnecting means for the new instantaneous hot water heater. See plumbing plans for additional information.
2018 IBC 107.2.1, 2017 NEC
09/20/2022 WILDAN BUILDING-COMMERCIAL REVIEW Approv-Cond Activity Number: T22CM06526

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Sheet G1 Provide accessible path of travel from the front door to Accessible parking and to the public way. Show location of Accessible Parking and signage.

Sheet A3 Provide accessible Restroom signage for UniSex Restroom.

Sheet A3 Provide roof plan showing location of roof drains and overflows. Per IBC

Sheet A4 Provide ADA seating per ICCA117



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
09/21/2022 PSHELTO1 FIRE REVIEW Approved