Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM06526
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/02/2022 | SHASEMA1 | ENGINEERING | REVIEW | Passed | |
| 09/08/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Revise the occupant load calculations to account for the fixed seats in the dining area (16 seats per sheet A4) and the order area (standing space at 5 square feet per person)in addition to the 2 occupants in the kitchen. Revise the number of required plumbing fixtures for the building accordingly. Reference: Sections 1004.5, 1004.6, and 2902.1, IBC 2018 |
| 09/08/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 09/08/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 09/09/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 09/09/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/14/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Show location and provide power and disconnecting means for the new instantaneous hot water heater. See plumbing plans for additional information. 2018 IBC 107.2.1, 2017 NEC |
| 09/20/2022 | WILDAN | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | Activity Number: T22CM06526 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. Sheet G1 Provide accessible path of travel from the front door to Accessible parking and to the public way. Show location of Accessible Parking and signage. Sheet A3 Provide accessible Restroom signage for UniSex Restroom. Sheet A3 Provide roof plan showing location of roof drains and overflows. Per IBC Sheet A4 Provide ADA seating per ICCA117 If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
| 09/21/2022 | PSHELTO1 | FIRE | REVIEW | Approved |