Permit Number: T22CM06493
Parcel: 123080330

Address:
2816 E HELEN ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM06493
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2022 SHASEMA1 ENGINEERING REVIEW Passed
08/29/2022 STEVE SHIELDS ZONING REVIEW Approved
08/29/2022 AWARNER1 NPPO REVIEW Approved
09/10/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM06493


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Indicate the designed live and dead loads for the structure on the drawings. Indicate the structure has been designed for a minimum wind speed is to be 115 mph per 3 second gust and the seismic category is B. Revise drawings if needed for new criteria.


BUILDING REVIEW COMMENTS:
Denied
1. Modify the general soil note 1 on sheet G1 that indicates an engineering report dated 2003. No such report was submitted.
2. Remove smoke detector notes, plumbing, HVAC and others that are not applicable to this project from the general notes on sheet G1. This appears to be a simple non-habitable accessory structure only.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
No mechanical work has been included with this submittal


ELECTRICAL REVIEW COMMENTS
Denied
1. Indicate all exterior lighting will be installed in accordance with the PIMA County regulations. Provide notes for the required fixture shading and light requirements for this project.
2. Update the general electrical note 4 on sheet G1 to indicate the current code. Note that a minimum of 90% of all lighting fixtures will contain high-efficacy lamps. 2018 IECC R404.1.
3. Note that all 15- and 20-amp outlets shall be tamper proof type. 2017 NEC 210.52.
4. Note that all exterior outlets shall be GFCI protected and be provided with a weatherproof enclosure with “in-use” covers. 2017 NEC 406.8.


PLUMBING REVIEW COMMENTS:
Conditionally Approved
No plumbing work has been included with this submittal


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov