Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T22CM06475
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/26/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM06475, T22CM06476 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied Please make corrections and resubmit. Resubmittal shall include a response letter. All code references are to the 2018 IBC unless otherwise noted. Recommend clouding changes to speed up the rereview. 1. Sheet S1.0 Typical 2 B.R. Unit notes "2 x 8 sistered joists at 16" O.C (each existing joist) but the existing joists at 12" O.C. Please clarify. 2. Provide load calculations for existing/new roof top mech'l. equipment as per IBC-CH. 16. 3. Provide pressure-treated wood at post base and column at masonry wall at details 1 and 2 on Sheet S1.0 as per IBC2304.12. 304.12 Protection Against Decay and Termites. Wood shall be protected from decay and termites in accordance with the applicable provisions of Sections 2304.12.1 through 2304.12.7. 4. Provide cut sheets of manufacturer's installation instructions for all engineered wood beams on Sheet S1.0 Typical 2 B.R. Unit as per IBC-107. 5. Provide Footing schedule with calculations of tributory loads and corresponding soil bearing capacities as per IBC2304.10.1 Fastener Requirements. The number and size of fasteners connecting wood members shall not be less than that set forth in Table 2304.10.1. FASTENING SCHEDULE 6. Provide Protection Against Termites at detail 6 on Sheet S1.0 as per IBC-2304.12. 304.12 . Wood shall be protected from termites in accordance with the applicable provisions of Sections 2304.12.1 through 2304.12.7. 7. Provide doumentation and location(s) where new footing(s) will be located as per IBC-107. 8. Provide Submittals to the Building Official as per IBC-1704.5 -In addition to the submittal of reports of special inspections and tests in accordance with Section 1704.2.4, reports and certificates shall be submitted by the owner or the owner's authorized agent to the building official for each of the following: a. Certificates of compliance for the fabrication of structural, load-bearing or lateral load-resisting members or assemblies on the premises of a registered and approved fabricator in accordance with Section 1704.2.5.1. b. Certificates of compliance for the seismic qualification of nonstructural components, supports and attachments in accordance with Section 1705.13.2. c. Certificates of compliance for designated seismic systems in accordance with Section 1705.13.3. d. Reports of mill tests in accordance with Section 20.2.2.5 of ACI 318 for reinforcing bars complying with ASTM A615 and used to resist earthquake-induced flexural or axial forces in the special moment frames, special structural walls or coupling beams connecting special structural walls of seismic force-resisting systems in structures assigned to Seismic Design Category B, C, D, E or F. 9. Provide a code analysis that includes the following: a. Use & Occupancy Classification as per Chapter 3. b. General Building Height & Areas as per Chapter 5. c. Type of Construction as per Chapter 6. d.Table 601- Fire-resistance ratings for building elements. e. Fire alarm yes/no 10.Provide details and locations for Duct and Air Transfer Openings in the Rated Floors per Section 713.4. 11.Provide wall sections and provide parapet height of 30-inches minimum between buildings. Section 705.11. 12.Recommend a minimum of 2 drains per areaway to prevent flooding due to blockage as per IPC-1108. 13.The requirements of Chapter 33, Safeguards During Construction and Demolition, shall be incorporated into the plan set. 14. Structural calculations need to include ponding based on the rate of flow through the roof drains and scuppers based on the rainfall for the region. Provide details for the number and discharge capacity of drains and overflow scuppers and size of openings. Roof plan shall show primary and secondary drains and drain patterns as per IBC-CH. 16. 15. Submit structural calculation in accordance with Chapter 16. The structural calculation shall include the following: A. Provide Wind Load Calculations (in the short direction) for the Building per Section 1609 of DC 2017 Building Code. B. Provide Seismic Calculations for the Building per Section 1613 of DC 2017 Building Code. Seismic calculations are to include 20 percent of the roof snow load in the effective seismic weight for roofs exceeding a flat roof snow load of 30 psf. Verify the snow load was applied to the effective seismic weight as required in ASCE-7 Section 12.7.2. C. Structural calculations shall include roof top equipment per Chapter 16. D. Structural calculations need to include ponding based on the rate of flow through the roof drains and scuppers based on the rainfall for the region per Chapter 16. Provide details for the number and discharge capacity of drains and overflow scuppers and size of openings. Roof plan shall show primary and secondary drains and drain patterns. BUILDING REVIEW COMMENTS: Denied Please make corrections and resubmit. Resubmittal shall include a response letter. All code references are to the 2018 IBC unless otherwise noted. Recommend clouding changes to speed up the rereview. 1. Sheet S1.0 Typical 2 B.R. Unit notes "2 x 8 sistered joists at 16" O.C (each existing joist) but the existing joists at 12" O.C. Please clarify. 2. Provide load calculations for existing/new roof top mech'l. equipment as per IBC-CH. 16. 3. Provide pressure-treated wood at post base and column at masonry wall at details 1 and 2 on Sheet S1.0 as per IBC2304.12. 304.12 Protection Against Decay and Termites. Wood shall be protected from decay and termites in accordance with the applicable provisions of Sections 2304.12.1 through 2304.12.7. 4. Provide cut sheets of manufacturer's installation instructions for all engineered wood beams on Sheet S1.0 Typical 2 B.R. Unit as per IBC-107. 5. Provide Footing schedule with calculations of tributory loads and corresponding soil bearing capacities as per IBC2304.10.1 Fastener Requirements. The number and size of fasteners connecting wood members shall not be less than that set forth in Table 2304.10.1. FASTENING SCHEDULE 6. Provide Protection Against Termites at detail 6 on Sheet S1.0 as per IBC-2304.12. 304.12 . Wood shall be protected from termites in accordance with the applicable provisions of Sections 2304.12.1 through 2304.12.7. 7. Provide doumentation and location(s) where new footing(s) will be located as per IBC-107. 8. Provide Submittals to the Building Official as per IBC-1704.5 -In addition to the submittal of reports of special inspections and tests in accordance with Section 1704.2.4, reports and certificates shall be submitted by the owner or the owner's authorized agent to the building official for each of the following: a. Certificates of compliance for the fabrication of structural, load-bearing or lateral load-resisting members or assemblies on the premises of a registered and approved fabricator in accordance with Section 1704.2.5.1. b. Certificates of compliance for the seismic qualification of nonstructural components, supports and attachments in accordance with Section 1705.13.2. c. Certificates of compliance for designated seismic systems in accordance with Section 1705.13.3. d. Reports of mill tests in accordance with Section 20.2.2.5 of ACI 318 for reinforcing bars complying with ASTM A615 and used to resist earthquake-induced flexural or axial forces in the special moment frames, special structural walls or coupling beams connecting special structural walls of seismic force-resisting systems in structures assigned to Seismic Design Category B, C, D, E or F. 9. Provide a code analysis that includes the following: a. Use & Occupancy Classification as per Chapter 3. b. General Building Height & Areas as per Chapter 5. c. Type of Construction as per Chapter 6. d.Table 601- Fire-resistance ratings for building elements. e. Fire alarm yes/no 10. The project information needs to include the accessibility requirements for Type A and Type B units. Show required and provided matrix showing compliance path that includes, but not limited to, the following information: Type A Units - Where there are ten (10) or more dwelling units intended to be occupied as a residence in a single structure, Type A accessible unit shall be provided in accordance with Chapter 10 of the ICC ANSI A117.1 standard as referenced from Chapter 11 of the Building Code. Section 1107.6.2 and 1107.2.2.2. Type B Units - Where there are four (4) or more dwelling units intended to be occupied as a residence in a single structure, every dwelling unit shall be a Type B accessible unit in accordance with Chapter 10 of the ICC ANSI A117.1 standard as referenced from Chapter 11 of the Building Code. Section 1107.6.2 and 1107.2.2.2. Exceptions: 1)The number of Type B units is allowed to be reduced in accordance with Section 1107.7, General Exceptions. General Exception 1107.7.3, Elevator service to the lowest story containing dwelling units, only the units on that story are required to be Type B units. 2)Type B units may contain the following adaptable features: 2.1) Shower compartment doors that are not accessible, but that can be removed without damaging the shower enclosure, provided that the mounting holes can be readily made watertight, and finishes extend behind the doors. Accessible units/spaces shall include toilet and bathing rooms, kitchen, living and dining areas and any exterior spaces, including patios, terraces, and balconies. Exceptions: 1)Stories and mezzanines exempted by Section 1107.4. 2)Recreational facilities in accordance with Section 1110.2. 3)Exterior decks, patios, or balconies that are part of Type B units and have impervious surfaces, and that are not more than 4- inches below the finished floor level of the adjacent interior space of the unit. Provide a Type B accessible detail sheet including dimensions. Floor plans shall show required clear maneuvering clearances at doors and all accessible areas in accordance with the ICC ANSI A117.1 standard. Note: Stacked washer and dryer are not accessible – side-by-side required in Type B units. 11. Per Section 1013.4, tactile exit signs shall be required at the following locations (common areas only): A)Wherever basic provisions require exit signs from a room or area to a corridor or hallway. The tactile exit sign shall have the words, “EXIT ROUTE.” B)Each grade-level exit door. The tactile exit sign shall have the word, “EXIT.” C)Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp. The tactile exit sign shall have the following words as appropriate: “EXIT STAIR DOWN.” “EXIT RAMP DOWN.” “EXIT STAIR UP.” “EXIT RAMP UP.” D)Each exit door that leads directly to a grade-level exterior exit by means of an exit enclosure or an exit passageway. The tactile exit sign shall have the words, “EXIT ROUTE.” 12. Provide door schedule with accessible hardware (lever type) as per IBC-1010.1.9.1. 13. Door hardware shall be installed 34-inches minimum and 48-inches maximum above the finished floor as per Section 1010.1.9.2. 14. Provide manufacturers specifications for dryers. Verify maximum vent piping allowed as per IBC-107. 15.Provide Rated Shaft Enclosures for dryer vent if located in a rated wall or floor assembly or passes through a rated assembly as per IBC-107. 16.Provide details and locations for Duct and Air Transfer Openings in the Rated Floors per Section 713.4. 17.Show location of shafts/chases serving the mechanical equipment closets for all units. Provide details on how the integrity of the rated assemblies is maintained as per IBC-107. 18. Exit signs and emergency lighting is required in all common areas that have 2 means of egress. Sections 1013 and 1008. 19.The alcove for toilets shall have a minimum width of 30 inches/15-inches to the centerline of the toilet/water closet. Looks like it complies but without a dimension it cannot be verified. Section 405.3.1 IPC. 20.Provide wall sections and provide parapet height of 30-inches minimum between buildings. Section 705.11. 21.Recommend a minimum of 2 drains per areaway to prevent flooding due to blockage as per IPC-1108. 22.Identify all tempered glazing per chapter 24 for hazardous locations. Entrance door sidelights shall comply. 23. Provide complete assembly descriptions for all rated assemblies based on the listing directory. The assembly descriptions shall include fasteners, stagger requirements, spacing of wall studs/framing, permitted wall cavity batts, and finish materials for seams and joints along with number and thickness of layers/coats. Per chapter 7. 24. Provide Minimum Room Widths on Floor Plans on sheets A1.0-A1.2. Habitable spaces, other than a kitchen, shall be not less than 7 feet in any plan dimension. Kitchens shall have a clear passageway of not less than 3 feet between counter fronts and appliances or counter fronts and walls as per IBC-1207.1 25. Provide Minimum Ceiling Heights on Floor Plans on sheets A1.0-A1.2. Occupiable spaces, habitable spaces and corridors shall have a ceiling height of not less than 7 feet 6 inches above the finished floor. Bathrooms, toilet rooms, kitchens, storage rooms and laundry rooms shall have a ceiling height of not less than 7 feet above the finished floor as per IBC-1207.2. 26. Provide Minimum Room Area on Floor Plans on sheets A1.0-A1.2. Every dwelling unit shall have not less than one room that shall have not less than 120 square feet of net floor area. Other habitable rooms shall have a net floor area of not less than 70 square feet as per IBC-1207.3. 27. The plans shall include the installation requirements for smoke detectors/alarms per code section 907.2.11.1 as follows: a)Permanently wired with battery backup power supply. b)When more than one smoke alarm is required to be installed, the alarm devices shall be interconnected in such a manner that the actuation of one alarm will activate all the alarms in the unit. c)Smoke detectors shall be located as follows: i)Inside each bedroom. ii)In the immediate vicinity of the bedrooms. iii)On each story, including basements. iv)They shall be not less than 3' from the door opening of a bathroom. v)They shall be at least 20' from a cooking appliance. Per manufacturer’s specifications. vi)They shall be at least 3' from supply registers of heating/cooling systems. Per manufacturer’s specifications vii)They shall be at least 3' from the tip of the blade of a ceiling-mounted fan. Per manufacturer’s specifications 28.The requirements of Chapter 33, Safeguards During Construction, shall be incorporated into the plan set. 29. Structural calculations need to include ponding based on the rate of flow through the roof drains and scuppers based on the rainfall for the region. Provide details for the number and discharge capacity of drains and overflow scuppers and size of openings. Roof plan shall show primary and secondary drains and drain patterns as per IBC-CH. 16. MECHANICAL REVIEW COMMENTS: Denied 1. Provide documentation and details of required Energy Utilization. Heating, ventilating and air-conditioning systems of all structures shall be designed and installed for efficient utilization of energy in accordance with the International Energy Conservation Code as per IMC 301.2. 2. Provide documentation and details of Vibration Isolation. Where vibration isolation of equipment and appliances is employed, an approved means of supplemental restraint shall be used to accomplish the support and restraint as per IMC 301.13. 3. Provide documentation and details of Penetrations of Floor/Ceiling/Wall Assemblies and Fire-Resistance-Rated Assemblies. Penetrations of wall/floor/ceiling assemblies and assemblies required to have a fire-resistance rating shall be protected in accordance with Chapter 7 of the International Building Code as per IMC 302.2. 4. Provide documentation and details of Installation. Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer's installation instructions and this code as per IMC 304.1. 5. Provide documentation and details for Structural Attachment of Hangers and anchors required to be attached to the building construction in an approved manner as per IMC 305.3. 6. Provide documentation and details of Condensate Disposal of Fuel-Burning Appliances & Liquid combustion by-products of condensing appliances shall be collected and discharged to an approved plumbing fixture or disposal area in accordance with the manufacturer's installation instructions. Condensate piping shall be of approved corrosion-resistant material and shall not be smaller than the drain connection on the appliance. Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than one eighth unit vertical in 12 units horizontal (1-percent slope) as per IMC 307.1. 7. Provide documentation and details of Drain Pipe Materials and Sizes. Components shall be selected for the pressure and temperature rating of the installation. Joints and connections as per IPC. Condensate waste and drain line size minimum 3/4 -inch internal diameter & not decrease in size to the place of condensate disposal. Where the drain pipes manifolded together for condensate drainage, the pipe or tubing shall be sized with Table 307.2.2 as per IMC 307.2.2. 8. Provide documentation and details of condensate drain trap as required by the equipment or appliance manufacturer as per IMC 307.2.4. 9. Provide documentation and details of required drain line maintenance. Condensate drain lines shall be configured to permit the clearing of blockages and performance of maintenance without requiring the drain line to be cut as per IMC 307.2.5. 10. Provide documentation and details of Location of Exhaust Outlets as per IMC 501.3.1. 11. Provide documentation and details in required Locking Access Port Caps. Refrigerant circuit access ports located outdoors shall be fitted with locking-type tamper-resistant caps (except roofs or locked access) as per IMC 1101.10. 12. Provide documentation and details of the Rigid Duct Penetrations. Duct system penetrations of walls, floors, ceilings and roofs and air transfer openings in such building components shall be protected as required by Section 607 as per IMC 603.7. 13. Provide documentation and details of Outdoor Airflow Rate. Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate, determined in accordance with this section. In each occupiable space, the ventilation system shall be designed to deliver the required rate of outdoor airflow to the breathing zone as per IMC Table 403.3.1.1. 14. Provide documentation and details of Balancing the ventilation air distribution system shall be provided with means to adjust the system to achieve not less than the minimum ventilation airflow rate as required by Sections 403.3 and 403.3.1.2. Ventilation systems shall be balanced by an approved method. Such balancing shall verify that the ventilation system is capable of supplying & exhausting the airflow rates required as per IMC 403.3.1.5. 15. Demolition & Construction to comply with IBC Chapter 33. ELECTRICAL REVIEW COMMENTS Denied Please make corrections and resubmit. Resubmittal shall include a response letter. All code references are to the NEC unless otherwise noted. Recommend clouding changes to speed up the rereview. 1. Personnel Doors. Where equipment rated 800A or more and there is a personnel door(s) intended for entrance to and egress from the working space less than 25ft from the nearest edge of the working space, the door(s) shall open in the direction of egress and be equipped with listed panic hardware. (110.26(C)(3)). 2. All nonlocking-type, 125-volt, 15- and 20-ampere receptacles located in guest rooms and guest suites shall be listed tamper-resistant receptacles. (406.13). 3. Determining the existing load of panels shall be per 220.87. 4. Provide voltage drop calculations for all conductors over 100 feet as per NEC. 5. Where the phase conductors are increased in size (e.g., for voltage drop compensation), the equipment grounding conductor shall be increased in size proportionately. (250.122(B)) 6. Feeders. Feeder conductors shall be sized for a maximum voltage drop of 2 percent at design load. Branch Circuits. Branch circuit conductors shall be sized for a maximum voltage drop of 3 percent at design load.(130.5(C)) 7. Verify #6 CU bond is secured to metallic piping (and not replaced with PEX) as required per Apt. Grounding diagram on sheet E6.0. 8. Show the service conductor routing from the utility service point as per NEC on sheet ES1.0. 9. Verify Service disconnect(s) shall be located nearest the point of entrance of the service entrance conductors. (230.70(A)). 10. Where a building or structure is supplied by more than one service, or any combination of branch circuits, feeders, and services, a permanent plaque or directory shall be installed at each service disconnect location denoting all other services, feeders, and branch circuits supplying that building or structure and the area served by each. 230.2(E) 11. Since more than one building is on the same property and under single management, verify each building is provided with means for disconnecting all ungrounded conductors. (225.31). 12. Verify occupants shall have access to their service disconnecting means for multiple occupancy buildings. (230.72(C)). 13. Verify Provide GFCI protection for all nonresidential kitchen and food service area receptacles (including receptacles dedicated to equipment) per 2016 [210.8(B)(2)]. 14. Since more than one building is supplied by a service, verify the grounded conductor supplying each building shall be adequately sized and grounded at each building or an equipment grounding conductor shall be provided from the main service to each building. (250.32 & 50). 15. Provide calculation to justify properly sized grounding conductors for equipment and raceway systems. Where ungrounded conductors are increased in size, equipment grounding conductors, where installed, shall be increased in size proportionately according to the circular mil area of the ungrounded conductors. (250.122). 16. Verify All equipment fastened in place or connected by permanent wiring method shall be connected to equipment grounding conductor. (250.110 & 112). 17. Indicate the burial depth of underground conduits and conductors and specify the cover material. (Table 300.5). 18. Provide cable supports on vertical runs. (300.7 (A)). 19. Provide rated electrical disconnect switch at direct connected electrical equipments/ appliances or lock-out device at circuit breakers. (422.31(B)). 20. The ungrounded and grounded conductors of each multi-wire branch circuit shall be grouped by wire ties or similar means in at least one location within the panelboard or other point of origination. (210.4(D)). 21. Each multiwire branch circuit shall be provided with a means that will simultaneously disconnect all ungrounded conductors at the point where the branch circuit originates. (210.4). 22. Multiwire branch circuits supplying power to the partition shall be provided with a mean to disconnect simultaneously all ungrounded conductors at the panelboard where the branch circuit originates. (605.7). 23. Note: A separate grounding conductor shall be installed in nonmetallic conduit runs. (352.60). 24. Provide permanent access to roof mounted equipment. (240.24, 430.102, 440.14). 25. Where a receptacle outlet is supplied by a branch circuit that required arc-fault circuit interrupter protection as specified elsewhere in this code, a replacement receptacle at this outlet shall be one of the following: (406.4(D)(4)). a) A listed outlet branch circuit type arc-fault circuit interrupter receptacle. b) A receptacle protected by a listed outlet branch circuit type arc-fault circuit interrupter type receptacle. c) A receptacle protected by a listed combination type arc-fault circuit interrupt type circuit breaker. PLUMBING REVIEW COMMENTS: Denied Please make corrections and resubmit. Resubmittal shall include a response letter. All code references are to the NEC unless otherwise noted. Recommend clouding changes to speed up the rereview. 1. Provide documentation and details on sheet P4.0 Cover Sheet of all plumbing products and materials shall be listed by a third-party certification agency. Products and materials shall be identified in accordance with Section 303.1 as required per IPC 303.4 Third-Party Certification. 2. Heat Traps. Demonstrate compliance of the required vertical pipe risers serving storage water heaters and storage tanks not having integral heat traps and serving a nonrecirculating system shall have heat traps on both the inlet and outlet piping as close as practical to the storage tank as per IPC 7.4.6. 3. Provide documentation and details on sheet P4.0 of the required Water Hammer arrestor. The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water-hammer arrestor shall be installed where quick-closing valves are utilized. Water-hammer arrestors shall be installed in accordance with the manufacturer's instructions. Water-hammer arrestors shall conform to ASSE 1010 as per IPC 604.9. 4. Provide documentation and details on sheet P4.0 Cover Sheet of required Water Conservation. The maximum water flow rates and flush volume for plumbing fixtures and fixture fittings shall comply with Section 604.4 as per IPC-401.3. 5. Provide documentation and details on sheet P5.0 Cover Sheet of Quality of Fixtures. Plumbing fixtures shall be constructed of approved materials, with smooth, impervious surfaces, free from defects and concealed fouling surfaces, and shall conform to standards cited in this code. Porcelain enameled surfaces on plumbing fixtures shall be acid resistant as per IPC- 402.1. 6. Provide documentation and details on sheet 000 Cover Sheet of Bathtub Enclosure. Doors in a bathtub enclosure shall conform to ASME A112.19.15 as per IPC- 407.4. 7. Verify Vent systems utilizing air admittance valves shall comply with this section. Stack-type air admittance valves shall conform to ASSE 1050. Individual and branch-type air admittance valves shall conform to ASSE 1051 as per IPC- 918.1 General. 8. Verify the valves shall be installed in accordance with the requirements of this section and the manufacturer's instructions. Air admittance valves shall be installed after the DWV testing required by Section 312.2 or 312.3 has been performed as per IPC- 918.2. 9. Verify Individual, branch and circuit vents shall be permitted to terminate with a connection to an individual or branch-type air admittance valve in accordance with Section 918.3.1. Stack vents and vent stacks shall be permitted to terminate to stack-type air admittance valves in accordance with Section 918.3.2 as per IPC- 918.3. 10. Verify horizontal branches. Individual and branch-type air admittance valves shall vent only fixtures that are on the same floor level and connect to a horizontal branch drain. Where the horizontal branch is located more than four branch intervals from the top of the stack, the horizontal branch shall be provided with a relief vent that shall connect to a vent stack or stack vent, or extend outdoors to the open air. The relief vent shall connect to the horizontal branch drain between the stack and the most downstream fixture drain connected to the horizontal branch drain. The relief vent shall be sized in accordance with Section 906.2 and installed in accordance with Section 905. The relief vent shall be permitted to serve as the vent for other fixtures as per IPC 918.3.1. 11. Verify Stack-type air admittance valves shall be prohibited from serving as the vent terminal for vent stacks or stack vents that serve drainage stacks having more than six branch intervals as per IPC 918.3.2. 12. Verify Location of Individual and branch-type air admittance valves shall be located not less than 4 inches above the horizontal branch drain or fixture drain being vented. Stack-type air admittance valves shall be located not less than 6 inches above the flood level rim of the highest fixture being vented. The air admittance valve shall be located within the maximum developed length permitted for the vent. The air admittance valve shall be installed not less than 6 inches above insulation materials as per IPC 918.4. 13. Verify Access and Ventilation. Access shall be provided to all air admittance valves. Such valves shall be installed in a location that allows air to enter the valve as per IPC-918.5. 14. Verify the Size of the air admittance valve shall be rated in accordance with the standard for the size of the vent to which the valve is connected as per IPC- 918.6. 15. Verify the Vent Required within each plumbing system, not less than one stack vent or vent stack shall extend outdoors to the open air as per IPC- 918.7. 16. Verify Prohibited Installations. Air admittance valves shall not be installed in non-neutralized special waste systems as described in Chapter 8 except where such valves are in compliance with ASSE 1049, are constructed of materials approved in accordance with Section 702.5 and are tested for chemical resistance in accordance with ASTM F1412. Air admittance valves shall not be located in spaces utilized as supply or return air plenums. Air admittance valves shall not be used to vent sumps or tanks except where the vent system for the sump or tank has been designed by an engineer. Air admittance valves shall not be installed on outdoor vent terminals for the sole purpose of reducing clearances to gravity air intakes or mechanical air intakes as per 918.8. 17. Verify the discharge piping on sheet P4.0 serving a pressure relief valve, temperature relief valve or combination thereof shall: Terminate not more than 6 inches above and not less than two times the discharge pipe diameter above the floor or flood level rim of the waste receptor & Discharge to a termination point that is readily observable by the building occupants as required per IPC 504.6. 18. Verify the required pan drain on sheet P4.0 shall extend full size and terminate over a suitably located indirect waste receptor or floor drain or extend to the exterior of the building and terminate not less than 6 inches and not more than 24 inches above the adjacent ground surface as required per IPC 504.7.2. 19. Provide detail of Water Heater Protection. Elevation of water heater ignition sources and mechanical damage protection requirements for water heaters shall be in accordance with the International Mechanical Code as per IPC- 502.1.1. 20. The project information needs to include the accessibility requirements for Type A and Type B units. Show required and provided matrix showing compliance path that includes, but not limited to, the following information: Type A Units - Where there are ten (10) or more dwelling units intended to be occupied as a residence in a single structure, Type A accessible unit shall be provided in accordance with Chapter 10 of the ICC ANSI A117.1 standard as referenced from Chapter 11 of the Building Code. Section 1107.6.2 and 1107.2.2.2. Type B Units - Where there are four (4) or more dwelling units intended to be occupied as a residence in a single structure, every dwelling unit shall be a Type B accessible unit in accordance with Chapter 10 of the ICC ANSI A117.1 standard as referenced from Chapter 11 of the Building Code. Section 1107.6.2 and 1107.2.2.2. Exceptions: 1)The number of Type B units is allowed to be reduced in accordance with Section 1107.7, General Exceptions. General Exception 1107.7.3, Elevator service to the lowest story containing dwelling units, only the units on that story are required to be Type B units. 2)Type B units may contain the following adaptable features: 2.1) Shower compartment doors that are not accessible, but that can be removed without damaging the shower enclosure, provided that the mounting holes can be readily made watertight, and finishes extend behind the doors. Accessible units/spaces shall include toilet and bathing rooms, kitchen, living and dining areas and any exterior spaces, including patios, terraces, and balconies. Exceptions: 1)Stories and mezzanines exempted by Section 1107.4. 2)Recreational facilities in accordance with Section 1110.2. 3)Exterior decks, patios, or balconies that are part of Type B units and have impervious surfaces, and that are not more than 4-inches below the finished floor level of the adjacent interior space of the unit. Provide a Type B accessible detail sheet including dimensions. Floor plans shall show required clear maneuvering clearances at doors and all accessible areas in accordance with the ICC ANSI A117.1 standard. Note: Stacked washer and dryer are not accessible – side-by-side required in Type B units. For the building entrances and all accessible unit entrances, show that the minimum strike edge distances are provided at the level area on the side to which a door (or a gate) swings, per Section 404.2.4: a)24" at exterior conditions. b)18" at interior conditions. c)12" on the push side, if the door has both a latch and a closer. d)Where a door is located in a recess or alcove where the distance from the face of the wall to the face of the door is greater than 8 inches, the above clearances shall apply. Section 404.2.4.3. Show a level area, or landing, per Section 404.2.4: e)60" in the direction of door swing. f)48" in the direction opposite the door swing (or 44" if doors don't have latches or closers). e)*ACCESSIBILITY CODE COMPLIANCE PATH NOTE: Based on the code path selected for compliance with accessibility, the code sections cited in this review may vary. Provide compliance path in your accessibility code matrix/table/sheet that identifies and details applicable requirements. Chapter 11, Dwelling Units and Sleeping Units, of the ICC ANSI A117.1 Standard as referenced, has 18 pages of requirements along with references to other chapters of the standard. I recommend adding an accessibility sheet to the plan set. If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
| 09/08/2022 | SHASEMA1 | ENGINEERING | REVIEW | Passed | |
| 09/08/2022 | PAUL CAMARENA | ZONING | REVIEW | Reqs Change | FROM: Paul Camarena PDSD Zoning Review Section PROJECT: T22CM06475, T22CM06476 Commercial 3122 E TERRA ALTA BL Zoning R-3 TRANSMITTAL DATE:?September 8, 2022 COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1.COMMENT: Units O and P are going from a studio to a one-bedroom apartment which will require additional parking a Development Package will be required. It appears that the site has limited parking, a parking reduction may be required. This can be a reduction based on providing additional bicycle parking If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov |
| 09/08/2022 | PCAMARE1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/19/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 09/26/2022 | JPEELDA1 | FIRE | REVIEW | Reqs Change | Respond to building comments. If using the 2018 IBC/IFC fire sprinklers would be required. If using the IEBC for a fire sprinkler "out" please reference the IEBC and levels of alterations in all areas. Questions: Jennifer Peel-Davis Jennifer.Peel-Davis@Tucsonaz.gov 520-837-7033 Fire Plans Examiner Tucson Fire Department |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/26/2022 | VVERA1 | OUT TO CUSTOMER | Completed |