Permit Number: T22CM06354
Parcel: 13734001D

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM06354
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2022 VFLORES1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change Unit # needed prior to issuance. You may contact Pima County Addressing Phone #:520-724-9512 Email: addressing@pima.gov
09/06/2022 SHASEMA1 ENGINEERING REVIEW Passed
09/07/2022 STEVE SHIELDS ZONING REVIEW Approved
09/07/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/14/2022 ROBERT SHERRY WATER REVIEW Completed
09/21/2022 JPEELDA1 FIRE REVIEW Reqs Change Denied
1. Sheet A1.0: The exit separation distance is measured incorrectly. Additionally, the measurement provided is not measured between two exits. Provide a correctly measured exit separation distance in accordance with Section 1007.1.1.1.
2. Sheet A1.0: The construction type listed is incomplete. Provide a corrected construction type in accordance with Chapter 6.
3. Sheet A1.0: The occupancy group provided doesn't match the occupancy groups on the egress plan. Provide a corrected occupancy class and a narrative as to the use of the space.
4. Sheet A1.0: Provide clarification about the adjacent tenant to ensure proper tenant separation.
5. Sheet A1.0: There are spaces that have not been counted in the occupant load calculation. Provide a space load calculation in accordance with Section. 1004.3.

Questions:

Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner
Tucson Fire Department
09/21/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM06354

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. Sheet A1.0: The exit separation distance is measured incorrectly. Additionally, the measurement provided is not measured between two exits. Provide a correctly measured exit separation distance in accordance with Section 1007.1.1.1.
2. Sheet A1.0: The construction type listed is incomplete. Provide a corrected construction type in accordance with Chapter 6.
3. Sheet A1.0: The occupancy group provided doesn't match the occupancy groups on the egress plan. Provide a corrected occupancy class and a narrative as to the use of the space.
4. Sheet A1.0: Provide clarification about the adjacent tenant to ensure proper tenant separation.
5. Sheet A1.0: There are spaces that have not been counted in the occupant load calculation. Provide a space load calculation in accordance with Section. 1004.3.
6. Sheet A2.0: Bathrooms are not permitted to be accessed through storage areas. Provide correctly accessible restrooms in accordance with Section 2902.3.1.


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Denied
1. Please provide a prescriptive path or provide COMcheck calculations for the lighting. All mandatory requirements must be identified on the plans for compliance. Reference IECC Section 505.1


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
09/21/2022 VVERA1 OUT TO CUSTOMER Completed