Permit Number: T22CM06351
Parcel: 140261100

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM06351
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2022 RPARSON1 OIP REVIEW Completed
09/02/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T22CM06351

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Conditionally Approved
1. Min. 3/4" conduit where 4 or more conductors are contained within the conduit per 2017 NEC - Chapter 9 - Tables.


PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
09/05/2022 NGARCIA3 OUT TO CUSTOMER Completed