Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM06285
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/03/2022 | PAUL CAMARENA | ZONING | REVIEW | Reqs Change | FROM: Paul Camarena PDSD Zoning Review Section PROJECT: T22CM06285 Addition 741 W SANDY ST Zoning R-2 TRANSMITTAL DATE: October 3, 2022 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1.COMMENT: Clarify the setbacks on the east side of the building,. The minimum required front street perimeter yard is 20 feet or one and one-half the height of the proposed wall (H), measured from the street property line , based on a wall height of 17’ 6” the required front street perimeter yard setback is 26’ 3” a Design Development Option (DDO) will need to be processed and approved to reduce the setback. DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. A DDO is a separate submittal from the building plan and shall be submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administration”. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov. If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov |