Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM06256
Parcel: 11452008G

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM06256
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/01/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Revise the site plan to show the size and route of the building sewer. Indicate the location of all of the cleanouts and, if noted on the approved sewer plan, the backwater valve. Reference: Section 107.2.1, IBC 2018.
09/01/2022 ROBERT SHERRY WATER REVIEW Reqs Change Provide calculations to verify that the proposed water meter from Tucson Water is of a sufficient size to serve the total water demand from the connected buildings (six duplexes and three SFR's in this case). Reference: Section 107.2.1, IBC 2018.
09/12/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Passed
09/13/2022 JGARCIA1 BUILDING-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/13/2022 VVERA1 OUT TO CUSTOMER Completed