Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM06252
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/01/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Revise the site plan to show the size and route of the building sewer. Indicate the location of all of the cleanouts and, if noted on the approved sewer plan, the backwater valve. Reference: Section 107.2.1, IBC 2018. |
| 09/01/2022 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Provide calculations to verify that the proposed water meter from Tucson Water is of a sufficient size to serve the total water demand from the connected buildings (six duplexes and three SFR's in this case). Reference: Section 107.2.1, IBC 2018. |
| 09/12/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 09/13/2022 | JGARCIA1 | BUILDING-COMMERCIAL | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/13/2022 | VVERA1 | OUT TO CUSTOMER | Completed |