Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM06185
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/12/2022 | RPARSON1 | OIP | REVIEW | Completed | |
| 09/02/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM06185 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied See comments under Building BUILDING REVIEW COMMENTS: Denied 1. Evaluation of existing roof framing for the additional dead loads and wind uplift loads./ Seems like in the submitted calculations Ballast weights were not included. 2. Furthermore, provide calculations to show that ballasted weight is higher than the overturning moment. 3. Provide complete details of the proposed ballasted system, pertinent details such as weight of ballast, how they are connected to the panels framing, approvals etc. Submitted information is inadequate to provide field inspections for the installation and for the review. MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/05/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |