Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM06183
Parcel: 11708247A

Address:
930 S 5TH AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM06183
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/16/2022 PAUL CAMARENA ZONING REVIEW Passed
08/16/2022 PCAMARE1 ENGINEERING REVIEW Passed
08/17/2022 PCAMARE1 NPPO REVIEW Passed
08/22/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T22CM06183
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet Zoning and other departmental requirements, conditions and concerns before permit approval.

MECHANICAL PLANS:

1. Provide an equipment specification list for any proposed or replaced equipment including the (fans, furnace and AC) size or capacity, M1302.1.

ELECTRICAL PLANS:

1. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2.
2. Show receptacle outlets at each kitchen counter space wider than 12” with no point along the wall line more than 24” from a receptacle outlet, E3901.4.1. Show receptacles within 2’ of counter edges or corners and no more than 4’ apart.
3. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3.
4. Show or notate a disconnect means or a locking breaker for the water heater, E4101.5.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review