Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM06175
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/12/2022 | RPARSON1 | OIP | REVIEW | Completed | |
| 08/30/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Approv-Cond | Activity Number: T22CM06175 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Conditionally Approved 1. Plans incorrectly reflect GEC (grounding electrode conductor) where it should reference EGC (equipment grounding conductor) if not associated with service equipment. PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/31/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |