Permit Number - T22CM06165
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/07/2022 WILDAN BUILDING-COMMERCIAL REVIEW Completed
10/12/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Previous plan review comments not addressed. Please provide the information requested on the line diagram plans. Previous comments:

“Please address the electrical plan review comments and provide a written response.

Ref; Electrical Line Diagrams.

1 Provide complete electrical 1-line/3-line diagram. Per definition the configuration and electrical service equipment shown in the line diagrams do not qualify as “Switchgear” per NEC art 100. Please remove the term “Switchgear” from the note above the Meter enclosure.

2 Indicate the rating of the new CT Cabinet, also size(s) of the feeder conduit, conductor quantities, types, between the new CT Cabinet and the gutter, or show what the letter ‘E’ designates.

3 Show the Grounding Electrode System on the plan, and indicate new or existing.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements”.

2018 IBC section 107.2.1; “[A] 107.2.1 Information on construction documents. Construction

documents shall be dimensioned and drawn on suitable

material. Electronic media documents are permitted to

be submitted where approved by the building official. Construction

documents shall be of sufficient clarity to indicate

the location, nature and extent of the work proposed and

show in detail that it will conform to the provisions of this

code and relevant laws, ordinances, rules and regulations, as

determined by the building official.