Permit Number: T22CM06165
Parcel: 12901100A

Address:
2185 E 20TH ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM06165
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2022 PSHELTO1 FIRE REVIEW Approved
08/30/2022 PCAMARE1 ENGINEERING REVIEW Passed
08/30/2022 PAUL CAMARENA ZONING REVIEW Approved
09/08/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Ref; Electrical Line Diagrams.

1 Provide complete electrical 1-line/3-line diagram. Per definition the configuration and electrical service equipment shown in the line diagrams do not qualify as “Switchgear” per NEC art 100. Please remove the term “Switchgear” from the note above the Meter enclosure.

2 Indicate the rating of the new CT Cabinet, also size(s) of the feeder conduit, conductor quantities, types, between the new CT Cabinet and the gutter, or show what the letter ‘E’ designates.

3 Show the Grounding Electrode System on the plan, and indicate new or existing.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
09/23/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM06165

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Denied
Plan sheet must be sealed by a professional registrant. ASRS 32-130


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
09/26/2022 NGARCIA3 OUT TO CUSTOMER Completed