Permit Number: T22CM06147
Parcel: 13109042A

Address:
5724 E 23RD ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM06147
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/15/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM06147
5724 E 23rd St - R-2
New SFR (3rd Review)

TRANSMITTAL: August 15, 2022
This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A.
1. Provide a height dimension on the Rear Elevations from design grade to the point where the wall meets the eave at the peak of the house.

2. Provide a lot coverage calculation that meets the requirements of UDC Article 6.4.3 and the example shown on the Residential Plot Plan Requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf,

3. Keynote 3 states “EASMENT (SEE ATTACHED DOCUMENTS)”. No documents were provided. Provide the recordation information on the plan and provided the recorded easement documents with the next submittal.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/15/2022 SSHIELD1 ENGINEERING REVIEW Passed
08/18/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T22CM06147
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SITE PLAN:

1. Show a street address for each dwelling on the site plan, R319.
2. Show a separate square footage of living space and covered patio, R106.1.1. Provide consistent dwelling square footage on sheet #1, 4 and 6.
3. Sewer lines passing through an easement require an agreement statement with a Pima County recorded document number, R106.1.1.

PLANS:

1. Provide manufacturer’s calculations and data for pre-engineered trusses dated and wet-sealed by an engineer who is registered in Arizona, or notate the requirement for deferred submittal, R106.1.

SECTIONS - DETAILS:

1. Show one-hour fire-resistive framed construction separating dwellings in compliance with IBC Table 721.1(2).
2. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation or need for providing air-impermeable rigid insulation at the roof, R806.
3. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.

PLUMBING PLANS:

1. Tucson Water Department limits flow rates for each water meter size in compliance with P2903.7. Show an appropriate yard pipe bypassing the existing dwelling and the water meter size.

MECHANICAL PLANS:

1. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D. Notate if the mechanical plans if system calculations will be provided by deferred submittal.

ELECTRICAL PLANS:

1. Update the code reference notated above Electric Notes.
2. Label a double breaker space for future Photo Voltaic on the panel schedule opposite end from the main/supply side, T103.9. Relocate the Future PV from space #19/21.
3. Show the location of the EV Charging receptacle on the plan.
4. Add the Electric Vehicle Charger entry to the load calculation. Include the Electric Vehicle load entry (typically 7680 watts) at the continuous demand section after the Total HVAC, N1104.2.2.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
(520) 837-4912 PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review
09/09/2022 AWARNER1 NPPO REVIEW Needs Review 7.7. Native Plant Preservation
Please identify vegetation to be impacted and show on plan. Native plants that are removed require a 2:1 replacement.